3.6 Outdoor sensor installation
The outdoor sensor (optional) must be positioned correctly
in order to ensure the climate control's proper functionality.
The sensor must be installed outside the building to be
heated, at approx. 2/3 the height of the NORTH or NORTH
WEST façade and far from flues, doors, windows and sun-
ny areas.
Fastening the outdoor sensor to the wall
- Unscrew the sensor protection box cover, turning it
anticlockwise to access the terminal board and fas-
tening holes
- Trace the fastening points using the box as a tem-
plate
- Remove the box and drill the holes for the 5x25 ex-
pansion plugs
- Fasten the box to the wall, using the two supplied
dowels
- unscrew the nut on the fair lead, and insert a bipolar
cable (with a cross section of 0.5 to 1mm
2
, not sup-
plied) to connect the probe to terminals 7 and 8 (see
the scheme in the chapter "Multi-row wiring diagram")
- connect the two cable wires to the terminal board
without identifying the polarities
- fully tighten the cable gland nut and close the protec-
tion box cover.
b
The sensor must be positioned on a smooth wall sec-
tion. If there are exposed bricks or irregular walls, an
area with a smooth contact must be prepared.
Fig. 13
b
The maximum length of the connection between the
outdoor sensor and the control panel is 50 m. In the
case of connections with a cable length that exceeds
50 m, check compliance of the value read on the card
with a real measurement and adjust parameter 39 to
make any necessary correction.
b
The connection cable between the outdoor sen-
sor and the control panel must not have couplings.
If these are necessary, they must be watertight and
suitably protected.
b
Any channelisation of the connection cable must be
separated by live cables (230Vac).
Correspondence table for all sensors
Measured temperatures (°C) - Resistive values of the sensors (Ω).
T (°C)
R (°Ω)
T (°C)
R (°Ω)
T (°C)
R (°Ω)
T (°C)
R (°Ω)
T (°C)
R (°Ω)
T (°C)
R (°Ω)
T (°C)
R (°Ω)
- 20 67739 - 1 28481 18 13062 37 6470 56 3426 75 1925 94 1137
- 19 64571 0 27279 19 12565 38 6247 57 3319 76 1870 95 1108
- 18 61568 1 26135 20 12090 39 6033 58 3216 77 1817 96 1079
- 17 58719 2 25044 21 11634 40 5828 59 3116 78 1766 97 1051
- 16 56016 3 24004 22 11199 41 5630 60 3021 79 1717 98 1024
- 15 53452 4 23014 23 10781 42 5440 61 2928 80 1669 99 998
- 14 51018 5 22069 24 10382 43 5258 62 2839 81 1622 100 973
- 13 48707 6 21168 25 9999 44 5082 63 2753 82 1577 101 948
- 12 46513 7 20309 26 9633 45 4913 64 2669 83 1534 102 925
- 11 44429 8 19489 27 9281 46 4751 65 2589 84 1491 103 901
- 10 42449 9 18706 28 8945 47 4595 66 2512 85 1451 104 879
- 9 40568 10 17959 29 8622 48 4444 67 2437 86 1411 105 857
- 8 38780 11 17245 30 8313 49 4300 68 2365 87 1373 106 836
- 7 37079 12 16563 31 8016 50 4161 69 2296 88 1336 107 815
- 6 35463 13 15912 32 7731 51 4026 70 2229 89 1300 108 796
- 5 33925 14 15289 33 7458 52 3897 71 2164 90 1266 109 776
- 4 32461 15 14694 34 7196 53 3773 72 2101 91 1232 110 757
- 3 31069 16 14126 35 6944 54 3653 73 2040 92 1199
- 2 29743 17 13582 36 6702 55 3538 74 1982 93 1168

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Beretta Power X 50 DEP R.S.I. and is the answer not in the manual?

Beretta Power X 50 DEP R.S.I. Specifications

General IconGeneral
BrandBeretta
ModelPower X 50 DEP R.S.I.
CategoryBoiler
LanguageEnglish

Related product manuals