10.5.1 External power supply unit
WARNING
Danger of lethal injury due to hazardous electric voltage
− Connect power supply units generating protective extra-low
voltage (24 V) only to supply voltages designed for these
power supply units. Note the overvoltage categories (refer to
the documentation of the power supply unit).
−
Do not apply the supply voltage to the protective extra-low
voltage.
All control components are supplied from 24 V voltage supplies (SELV/PELV).
Use the Bosch Rexroth power supply unit VAP01.1H-W23-024-010-NN, part number R911171065,
for the logic supply. For further information on the external power supply unit and on the creation of
overvoltage categories, refer to the documentation of the power supply unit.
All lines of the 24 V voltage supply have to be routed separately from lines carrying higher voltages.
All peripherals, such as digital sensors or actuators connected to the interfaces of the control, also have
to comply with the criteria of safety-separated circuits.
The 24 V voltage supply can be grounded. For more detailed information, refer to the docu-
mentation of the power supply unit.
Use only power supply units that can bridge a half-wave failure (10 ms).
10.5.2 Power connector XD10
The control is supplied via the XD10 plug.
Connect the power connector with cables with a conductor cross-section of AWG 16
(1.5 mm
2
).
Use only copper wires to connect the connection terminals.
Use only cables approved for temperatures of at least 60°C.
Only the power connector is permitted to connect the 24 V supply voltage for the control (see
⮫ Chapter 5.1 Power connectors, 24 V on page 11).
Fig. 11: Power connector XD10
Mounting, dismounting and electric installation