EasyManuals Logo
Home>Carrier>Controller>RTU Open

Carrier RTU Open User Manual

Carrier RTU Open
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #20 background imageLoading...
Page #20 background image
20
Purge Time – The maximum amount of time used for a pre-
occupancy purge.
Range = 0 to 240 minutes
Default = 60 minutes
Unocc Free Cool Enable – Set to enable or disable the econo-
mizer for night time free cooling (NTFC) operation.
Range = Disable/Enable
Default = Disable
Setpoint Separation – Sets the minimum separation gap in
which setpoints can be set.
Range = 2 to 10°F
Default = 5°F
Occupancy Source – Tells the controller which method of oc-
cupancy control to use in determining occupancy of the roof-
top. Refer to Occupancy in the operation section for detail on
each specific operation function.
Range = Always Occupied, BACnet Schedule, BAS On/Off,
or Remote Occ Input
Default = Always Occupied
INPUTS
Input 1 Function – This input is an analog input and can be
configured to be one of four different inputs: No Sensor, IAQ
Sensor, OAQ Sensor, or Space RH Sensor. Input 1 is wired to
pin J4-4,5,6.
Default = No Sensor
Input 2 Function – This input is an analog input and can be
configured to be one of four different inputs: No Sensor, IAQ
Sensor, OAQ Sensor, or Space RH Sensor. Input 2 is wired to
pin J4-1,2,3
Software Default = No Sensor
Factory Default = IAQ Sensor with factory-installed CO
2
sensor
NOTE: For Inputs 1 and 2, if using Carrier air quality sensors do
not use 24Vdc from RTU Open board. External 24Vdc power sup-
ply required.
Input 3 – This input is a discrete input and can be configured
to be one of six different functions: No Function, Compressor
Safety, Fan Status, Filter Status, Remote Occupancy, or Door
Contact. This input can also be configured to be either a Nor-
mally Open (N/O) or a Normally Closed (N/C) switch. Input 3
is factory wired to pin J1-2. Field accessories can be wired to
its parallel pin J5-5.
Factory Default = Compressor Safety and N/O
Input 5 – This input is a discrete input and can be configured
to be one of six different functions: No Function, Fire Shut-
down, Fan Status, Filter Status, Remote Occupancy, or Door
Contact. This input can also be configured to be either a Nor-
mally Open (N/O) or a Normally Closed (N/C) switch. Input 5
is factory wired to pin J1-10. Field accessories can be wired to
its parallel pin J5-3.
Software Default = Fire Shutdown and N/C
Factory Default = Fire Shutdown and N/O
Input 8 – This input is a discrete input and can be configured
to be one of six different functions: No Function, Enthalpy
Switch, Fan Status, Filter Status, Remote Occupancy, or Door
Contact. This input can also be configured to be either a Nor-
mally Open (N/O) or a Normally Closed (N/C) switch. Input 8
is factory wired to pin J2-6. Field accessories can be wired to
its parallel pin J5-1.
Software Default = Enthalpy Switch and N/O
Factory Default = No Function and N/O without factory-in-
stalled enthalpy sensor
Input 9 – This input is a discrete input and can be configured
to be one of seven different functions: No Function, Humidi-
stat, Fan Status, Filter Status, Remote Occupancy, Door Con-
tact, or IGC Override. This input can also be configured to be
either a Normally Open (N/O) or a Normally Closed (N/C)
switch. Input 9 is factory and field wired to pin J5-7.
Factory Default = Humidistat and N/O
NOTE: For 48LC 07-26 Units (gas heat units) this decision is
automatically set to IGC Override and is factory wired.
Space Sensor Type – This tells the controller what type of
space sensor is installed to run the unit. The four types that can
be used are: a standard 10k Type II thermistor (T55), sensor
with a setpoint offset slider bar (T56), or a communicating sen-
sor (SPT Sensor) and, ZS Sensor.
Range = T55, T56 (Use for T59), SPT Sensor, or ZS Sensor
Default = T55
ZS Sensor Type – The type of local space temperature sensor.
Range = ZS Base, ZS Plus, ZS Pro
Default = None
T5x Override Duration – Sets the override time duration the
unit will change from unoccupied to occupied when the over-
ride button is pushed on the space sensor.
Range = 0-24 hours
Default = 1 hour
Rnet Port – input for communicating sensor or Equipment
Touch™ Terminal J13 - 1, 2, 3, 4
Range = SPT Sensor, ZS Sensor, or Equipment Touch
Default = None
SERVICE CONFIGURATION
Unit Type – This tells the control what type of unit it is con-
trolling. Heat/Cool refers to gas and electric heat units. LC
WeatherExpert
®
refers to a special 3 stage/2 compressor unit.
HP O/B Ctrl refers to a heat pump unit which requires revers-
ing valve control. HP Y1/W1 Ctrl refers to a heat pump unit
whose reversing valve is built in to the cooling or heating call.
This decision is factory configured for the specific unit type as
supplied.
NOTE: When unit type is set to LC WeatherExpert other configu-
ration settings in the Service Configuration menu will become
hidden from user's view. The configurations that become hidden
include Compressor Stages, Face Split Coil, Fan Control.
Compressor Stages – This refers to the number of mechanical
cooling stages available on a specific unit. For LC size 07-26
units this setting is “Three Stage” and is not a visible menu
configuration.
Factory Default = “Three Stage” for LC size 07-26 units .
Economizer Exists – This indicates if there is an economizer
installed on the unit.
Factory Default = NO if no economizer, or YES if there is
an economizer installed.
Fan Control – This refers to the type of fan control for the given
unit. If Unit Type is selected to LC WeatherExpert, then this is set
to Variable Speed, and is not a visible menu configuration.
Factory Default = Variable Speed for LC size 07-26 units
and FC/GC units
VFD Input – Defines the electrical control signal used by the
VFD's input. Applies to Variable Speed fan control only.
Range = 2-10VDC or 0-10VDC
Factory Default = 2-10 VDC and 0-10VDC on FC/GC units
Show VFD Config As Sets the VFD control in terms of Per-
centage for typical VFDs or Voltage for ECM motor control.
Factory Default = Percentage

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier RTU Open and is the answer not in the manual?

Carrier RTU Open Specifications

General IconGeneral
BrandCarrier
ModelRTU Open
CategoryController
LanguageEnglish

Related product manuals