IGS-NT Communication Guide
137
Exceptional response
Byte Meaning Note
0 Controller address Same as in the query
1 131 Modbus fun.number 128
2 2 see Error list on page 150
3
4
Check field CRC
lower byte (LSB)
upper byte (MSB)
see Check field calculation on page 143.
Write Single Registers
Query
Byte Meaning Note
0 Controller address 1 to 32
1 6 Modbus function code
2
3
Communication object number
upper byte (MSB)
lower byte (LSB)
4
5
Data
upper byte (MSB)
lower byte (LSB)
6
7
Check field CRC
lower byte (LSB)
upper byte (MSB)
see Check field calculation on page 143
Standard response
Byte Meaning Note
0 Controller address Same as in the query
1 6 Same as in the query
2
3
Communication object number
upper byte (MSB)
lower byte (LSB)
Same as in the query
4
5
Data
upper byte (MSB)
lower byte (LSB)
Same as in the query
6
7
Check field CRC
lower byte (LSB)
upper byte (MSB)
see Check field calculation on page 143

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliGen NT BaseBox and is the answer not in the manual?

ComAp InteliGen NT BaseBox Specifications

General IconGeneral
BrandComAp
ModelInteliGen NT BaseBox
CategoryController
LanguageEnglish

Related product manuals