IGS-NT Communication Guide
138
Exceptional response
Byte Meaning Note
0 Controller address Same as in the query
1 134 Function code + 128
2 2 see Error list on page 150
3
4
Check field CRC
lower byte (LSB)
upper byte (MSB)
see Check field calculation on page 143
Write Multiple Registers
Query
Byte Meaning Note
0 Controller address 1 to 32
1 16 Modbus function code
2
3
Communication object number
upper byte (MSB)
lower byte (LSB)
4
5
Communication object length expressed by the number of
registers
upper byte (MSB)
lower byte (LSB)
Greater than 0
6 Length of written data in bytes (L) Number of registers = 2
7
8
Data of the 1st register
upper byte (MSB)
lower byte (LSB)
9
10
Data of the 2nd register
upper byte (MSB)
lower byte (LSB)
...
L + 5
L + 6
Data of the last register
upper byte (MSB)
lower byte (LSB)
L + 7
L + 8
Check field CRC
lower byte (LSB)
upper byte (MSB)
see Check field calculation on
page 143

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliGen NT BaseBox and is the answer not in the manual?

ComAp InteliGen NT BaseBox Specifications

General IconGeneral
BrandComAp
ModelInteliGen NT BaseBox
CategoryController
LanguageEnglish

Related product manuals