16.
K-Factor Settings
Changing the Maximum Flow
If this setting is left at 0000 the maximum flow, or Qmax, is 40 litres/minute by default. When
changing the maximum flow, note that the high flow cutoff, low flow cutoff (LPG only), MMQ,
and preset rounding are calculated from the maximum flow.
See Using the Dispenser Menus to edit these settings. Use the procedure for both side A and B.
Changing the K-Factor
The K-Factor is used to calibrate product flow. It is a ratio of litres dispensed per revolution of
the meter. The K-Factor may need to be calibrated after periods of time. To calibrate the pump,
dispense fuel into a certified measuring container and compare the display value with the one
dispensed.
Example:
Display shows 10.00 True volume 20.00
To calculate the correct K-Factor from the information above; firstly record the existing K-Factor.
 





 
See Using the Dispenser Menus to edit these settings. Use the procedure for both side A and B.
qa 0000
fA
001.0000