A flow range is needed for each pump to dispense an accurate amount of product. If too much
or too little fuel is dispensed, the meter can not accurately measure the dispensed fuel and
therefore should cut off and display an end of sale message.
The low-flow cutoff will end the transaction (without an error code) if flow drops below this
value. In LPG operation, the default value for the low flow cutoff is 0.1x the maximum flow. For
example, if the maximum flow was 40L/min (the default):
If a custom value is desired, enter the value in this menu in litres. In non-LPG mode, the low-
flow cutoff only applies if a custom value is entered.
See Using the Dispenser Menus to edit these settings. Use the procedure for both side A and B.
The high-flow cutoff will stop transactions if the flowrate exceeds this value, and will return an
error. For LPG operation the default value for the high flow cutoff is 1.5x the maximum flow. For
example, if the maximum flow was 40L/min (the default):
If a custom value is desired, enter the value in this menu in litres. In non-LPG mode, the high-
flow cutoff only applies if a custom value is entered.
See Using the Dispenser Menus to edit these settings. Use the procedure for both side A and B.