EasyManuals Logo
Home>Daikin>Air Conditioner>Super Multi Plus E-Series RMXS112E8V1B

Daikin Super Multi Plus E-Series RMXS112E8V1B User Manual

Daikin Super Multi Plus E-Series RMXS112E8V1B
492 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #342 background imageLoading...
Page #342 background image
Troubleshooting with LED SiBE18-821_C
330 Troubleshooting
1.2 BP Unit
i
: ON,
h
: OFF,
j
: Blinks, —: No matter
Green : Blinks in normal condition
Red : OFF in normal condition
Note: Turn the power off then on again. If the LED display recurs, the BP unit PCB is defective.
BP Unit LED Indication Description
Green Red
A1234
jhhhh
Normal condition
jih hh
Defective electronic expansion valve or anti-icing control in non-operating
indoor unit
jiih h
Defective thermistor
jihii
Freeze-up protection control in operating indoor unit or standby indoor unit
i
— — — — Defective BP unit PCB (see note.)
h
— — — — Power supply abnormality (see note.)
LEDA (H1P)
LED1 (H2P)
LED2 (H3P)
LED3 (H4P)
LED4 (H5P)
(Q0395)