18 | Piping installation
Installer and user reference guide
76
RXMLQ8 + RXYLQ10~14T7Y1B*
VRV IV system air conditioner
4P543427-1A – 2020.10
Maximum allowable height difference
H1 ≤50m (40m)
(if outdoor is located below indoor units)
Conditional extension up till 90m is possible without additional option
kit:
In case the outdoor location is higher than indoor: extension is possible
up till 90m and following 2conditions must be fulfilled:
- Liquid piping size up (see table "Size up" in "E: Piping between
refrigerant branch kit and indoor unit"[470]).
- Dedicated setting on outdoor unit is required (see [2‑49] in "Mode 2:
Field settings"[4120]).
In case the outdoor location is lower than indoor: extension is possible
up till 90m and following 6conditions must be fulfilled:
- 40~60m: minimum connection ratio connected: 80%.
- 60~65m: minimum connection ratio connected: 90%.
- 65~80m: minimum connection ratio connected: 100%.
- 80~90m: minimum connection ratio connected: 110%.
- Liquid piping size up (see table "Size up" in "E: Piping between
refrigerant branch kit and indoor unit"[470]).
- Dedicated setting on outdoor unit is required (see [2‑35] in "Mode 2:
Field settings"[4120]).
H2 ≤30m
H3 ≤5m
Maximum allowable length after branch
The pipe length from the first refrigerant branch kit to the indoor unit ≤40 m.
Example 1.1: unit 8: b+c+d+e+f+g+p≤40m
Example 1.2: unit 6: b+h≤40m, unit 8: i+k≤40m
Example 1.3: unit 8: i≤40m
However, extension is possible if all below conditions are met. In this case
limitation can be extended up to 90m.
H1
1
2
3
a
A
h i j k l m n
B C D E F G
pb c d e f
1 2 3 4 5 6 7
8
g
H2
1 Outdoor unit
2 Refnet joints (A~G)
3 Indoor units (1~8)
Conditions:
a The piping length between all indoor units to the nearest branch kit is ≤40m.
Example: h, i, j … p≤40m

Table of Contents

Other manuals for Daikin VRV IV

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin VRV IV and is the answer not in the manual?

Daikin VRV IV Specifications

General IconGeneral
TypeVariable Refrigerant Volume (VRV)
SeriesVRV IV
RefrigerantR410A
Energy EfficiencyHigh
Operating Temperature Range (Cooling)-5°C to 46°C
Operating Temperature Range (Heating)-20°C to 15.5°C
InstallationProfessional installation required
ControlCentralized control system
Indoor Unit OptionsVarious types including ceiling cassette, wall-mounted, ducted, and floor-standing
Power Supply380-415V, 3-phase, 50Hz

Related product manuals