2 | General safety precautions
Installer and user reference guide
9
RXMLQ8 + RXYLQ10~14T7Y1B*
VRV IV system air conditioner
4P543427-1A – 2020.10
CAUTION
Do NOT place any objects or equipment on top of the unit.
Do NOT sit, climb or stand on the unit.
NOTICE
Works executed on the outdoor unit are best done under dry weather conditions to
avoid water ingress.
In accordance with the applicable legislation, it might be necessary to provide a
logbook with the product containing at least: information on maintenance, repair
work, results of tests, stand-by periods,…
Also, at least, following information MUST be provided at an accessible place at the
product:
Instructions for shutting down the system in case of an emergency
Name and address of fire department, police and hospital
Name, address and day and night telephone numbers for obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.
2.1.2 Installation site
Provide sufficient space around the unit for servicing and air circulation.
Make sure the installation site withstands the weight and vibration of the unit.
Make sure the area is well ventilated. Do NOT block any ventilation openings.
Make sure the unit is level.
Do NOT install the unit in the following places:
In potentially explosive atmospheres.
In places where there is machinery that emits electromagnetic waves.
Electromagnetic waves may disturb the control system, and cause malfunction of
the equipment.
In places where there is a risk of fire due to the leakage of flammable gases
(example: thinner or gasoline), carbon fibre, ignitable dust.
In places where corrosive gas (example: sulphurous acid gas) is produced.
Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
2.1.3 Refrigerant — in case of R410A or R32
If applicable. See the installation manual or installer reference guide of your
application for more information.
NOTICE
Make sure refrigerant piping installation complies with applicable legislation. In
Europe, EN378 is the applicable standard.
NOTICE
Make sure the field piping and connections are NOT subjected to stress.

Table of Contents

Other manuals for Daikin VRV IV

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin VRV IV and is the answer not in the manual?

Daikin VRV IV Specifications

General IconGeneral
TypeVariable Refrigerant Volume (VRV)
SeriesVRV IV
RefrigerantR410A
Energy EfficiencyHigh
Operating Temperature Range (Cooling)-5°C to 46°C
Operating Temperature Range (Heating)-20°C to 15.5°C
InstallationProfessional installation required
ControlCentralized control system
Indoor Unit OptionsVarious types including ceiling cassette, wall-mounted, ducted, and floor-standing
Power Supply380-415V, 3-phase, 50Hz

Related product manuals