2.1.10 IT mains
IT mains
Do not connect frequency converters with RFI-filters to mains supplies with a voltage between phase and earth of more than 440 V
for 400 V converters and 760 V for 690 V converters.
For 400 V IT mains and delta earth (grounded leg), mains voltage may exceed 440 V between phase and earth.
For 690 V IT mains and delta earth (grounded leg), mains voltage may exceed 760 V between phase and earth.
Par. 14-50
RFI Filter
can be used to disconnect the internal RFI capacitors from the RFI filter to ground.
2.1.11 Software Version and Approvals: ADAP-KOOL Drive AKD 102
ADAP-KOOL Drive AKD 102
Software version: 2.1.x
This manual can be used with all ADAP-KOOL Drive AKD 102 frequency converters with software version 2.1.x.
The software version number can be seen from par. 15-43
Software Version
.
2.1.12 Disposal instruction
Equipment containing electrical components must not be disposed of together with domestic waste.
It must be separately collected with electrical and electronic waste according to local and currently valid leg-
islation.
ADAP-KOOL
®
Drive AKD 102 High Power 2 Safety
MG.11.O1.02 - ADAP-KOOL
®
is a registered Danfoss trademark
11
2

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ADAP-KOOL AKD 102 and is the answer not in the manual?

Danfoss ADAP-KOOL AKD 102 Specifications

General IconGeneral
BrandDanfoss
ModelADAP-KOOL AKD 102
CategoryController
LanguageEnglish

Related product manuals