EasyManuals Logo
Home>Danfoss>Controller>AK-CH 650

Danfoss AK-CH 650 User Manual

Danfoss AK-CH 650
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
AK-CH 650 Capacity controller RS8ER302 © Danfoss 2016-02 13
Point
Signal Signal
type
S
Pt 1000 ohm/0°C
S1
S2
Saux1
Saux2
SSA
SdA
Pt 1000
P
AKS 32R
AKS 32
P0A
P0B
PcA
PcB
AKS 32R /
AKS 2050 /
MBS 8250
-1 - xx bar
AKS 32
-1 - zz bar
U
...
0 - 5 V
0 - 10 V
On/O Ext.
Main
switch
Day/
Night
Door
Active at:
Closed
/
Open
DO
AKV
Comp 1
Comp 2
Fan 1
Alarm
Light
Rail heat
Defrost
Active at:
On
/
O
Option Board
Please see the signal
on the page with the
module.
Signal Module Point
Terminal
Signal type /
Active at
1
1 (AI 1) 1 - 2
2 (AI 2) 3 - 4
3 (AI 3) 5 - 6
4 (AI 4) 7 - 8
5 (AI 5) 9 - 10
6 (AI 6) 11 - 12
7 (AI 7) 13 - 14
8 (AI 8) 19 - 20
9 (AI 9) 21 - 22
10 (AI 10) 23 - 24
11 (AI 11) 25 - 26
12 (DO 1) 31 - 32
13 (DO 2) 33 - 34
14 (DO 3) 35 - 36
15 (DO 4) 37 - 38
16 (DO 5) 39 - 40 - 41
17 (DO6) 42 -43 - 44
18 (DO7) 45 - 46- 47
19 (DO8) 48 - 49 -50
24 -
25 -
Terminal 15: 12 V
Terminal 16: 5 V
Terminal 27: 12 V
Terminal 28: 5 V
Terminal
17, 18, 29, 30:
(Cable screen)
Solid state outputs
on 12 - 15
Relay or AKV coil
fx 230 V a.c.
Relay outputs on
16 - 19
Analog
inputs
on 1 - 11
Point 1 2 3 4 5 6 7 8 9 10 11
Type AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8 AI9 AI10 AI11
Point 12 13 14 15 16 17 18 19
Type DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8
24 and 25 used
only when "Op-
tion board tted"
3: Brown
2: Blue
1: Black
3: Brown
2: Black
1: Red
AKV

Table of Contents

Other manuals for Danfoss AK-CH 650

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss AK-CH 650 and is the answer not in the manual?

Danfoss AK-CH 650 Specifications

General IconGeneral
BrandDanfoss
ModelAK-CH 650
CategoryController
LanguageEnglish

Related product manuals