Service
Table 20: Service
Control state
Here the actual control state of the controller can be readout:
• (0) S0=Normal ctrl.
• (1) S1=Wait after defrost
• (2) S2=Min ON timer
• (3) S3=Min OFF timer
• (4) S4=Drip o
•
(10) S10=Main switch OFF
• (11) S11=Thermostat cutout
• (14) S14=Defrost
• (15) S15=Fan delay
•
(17) S17=Door open
•
(20) S20=Emergency control
•
(25) S25=Manual control
• (30) S30=Pulldown cycle
• (32) S32=Powerup delay
• (33) S33=Heating
Air temperature
Temperature measured with Sair sensor.
S5 Evaporator temperature
Temperature measured with S5 sensor
Status of DI1 input
Status on DI1 input. on/1=closed
Night condition
Status on night operation (on or o)
Status of DI2 input
Status on DI2 input. on/1=closed
Actual reference
Read the present temperature regulation reference
Compressor / Liquid line solenoid valve
Status on relay for cooling
Fan relay
Status on relay for fan
Defrost relay
Status on relay for defrost
Alarm relay
Status on relay for alarm
Light relay
Status on relay for light
Controller code no.
Last 4 ciers of controller code no.
Heat relay
Status on relay for heating element
Sc Condenser temperature
Temperature measured with Sc sensor
EKC 223, 224 display menu
Conguration
Table 21: Conguration
Main switch (-1=service / 0=OFF / 1=ON)
Selection of application mode.
The controller can be dened in various ways. Here you set
which of the 4 applications is required.
Please refer to Wiring diagrams for the controller in question.
Sensor type selection
(0) n5 = NTC 5k, (1) n10 = NTC 10k, (2) Pt = Pt1000, (3) Ptc = PTC
1000
© Danfoss | Climate Solutions | 2023.05 BC432222569027en-000201 | 29
Case controller, type EKC 223 and EKC 224