Sensor type selection
(0) n5 = NTC 5k, (1) n10 = NTC 10k, (2) Pt = Pt1000, (3) Ptc = PTC
1000
Display resolution
(0) 0.1 , (1) 0.5 , (2) 1.0
Max. standby time after coordinated defrost
DI2 conguration
(0) oFF=not used, (1) Sdc=status, (2) doo=door function, (3)
doA=door alarm, (4) SCH=main switch, (5) nig=day/night mode,
(6) rFd=reference displacement, (7) EAL=external alarm, (8)
dEF=defrost, (9) Pud=pull down
Conguration of light function
(0) on=always on, (1) dAn=day/night, (2) doo=based on door
action, (3) nEt = Network
Light control via network (only if o38=3 (nEt))
Selection of application mode.
The controller can be dened in various ways. Here you set
which of the 4 applications is required.
Please refer to the Wiring diagrams for the controller in ques-
tion.
Quick presetting of primary parameters
0 = Not used
1 = MT, Natural defrost, stop on time
2 = MT, El defrost, stop on time
3 = MT, El defrost, stop on temp.
4 = LT, El defrost, stop on temp
5 = Room, MT, El defrost, stop on time
6 = Room, MT, El defrost, stop on temp.
7 = Room, LT, El defrost, stop on temp.
Replace the controllers factory settings with the present set-
tings
Display at defrost
(0) Air=Sair temperature
(1) FrE=freeze temperature
(2) -d-=”-d-” is displayed
(1)
Parameter can only be changed while r12 Main switch is in position OFF.
(1)
Parameter can only be changed while r12 Main switch is in position OFF.
Polarity
Table 28: Polarity
Invert alarm relay
(1) = Invert relay action
Service
Table 29: Service
S5 Evaporator temperature
Actual thermostat reference
Compressor / Liquid line solenoid valve
Case controller, type EKC 223 and EKC 224
© Danfoss | Climate Solutions | 2023.05 BC432222569027en-000201 | 32