Defrost
Table 24: Defrost
Defrost method
(0) non = None, (1) nat = Natural, (2) El = Electrical, (3) gas = Hot
gas
Interval between defrost starts
Time oset for start of rst defrost at start-up
Delay for fan start after defrost
Fan operation during defrost
Defrost sensor (0=time, 1=Sair, 2=S5)
Max. comp. runtime between two defrosts
Defrost on demand - S5 temperature’s permitted variation dur-
ing frost build-up. On central plant choose 20 K (=o)
Defrost delay after pull-down (0 = OFF)
(1)
This menu can only be set when regulation is stopped, i.e. “r12” is set to 0.
(1)
This menu can only be set when regulation is stopped, i.e. “r12” is set to 0.
Fan
Table 25: Fan
Fan at stop of compressor
(0) FFC = Follow comp., (1) Fao = ON, (2) FPL = Fan pulsing
Fan stop temperature (S5)
Compressor
Table 26: Compressor
Compressor OFF delay at door open
Miscellaneous
Table 27: Miscellaneous
Delay of outputs at start-up
DI1
conguration
(0) oFF=not used, (1) Sdc=status, (2) doo=door function, (3)
doA=door alarm, (4) SCH=main switch, (5) nig=day/night mode,
(6) rFd=reference displacement, (7) EAL=external alarm, (8)
dEF=defrost, (9) Pud=pull down, (10) Sc=condenser sensor
© Danfoss | Climate Solutions | 2023.05 BC432222569027en-000201 | 31
Case controller, type EKC 223 and EKC 224