6 Conguration
6.1 Driver Mode
In this mode The EKE 1x is acting as stepper motor valve driver, where master is commanding the valve opening
degrees to the EKE controller. In this mode, no sensor is needed as we are not doing any superheat control. The
control signal can be:
• Analog signal e.g., 0 – 10 V or 4 – 20 mA
• Bus communication via RS485 (Modbus RTU)
Figure 55: Driver mode
6.1.1 Driver Mode using analog signal
The signal can be used to drive the valve’s opening degree to a desired position. This feature is used to drive the
stepper motor valve to the desired level.
Figure 56: Driver Mode using analog Signals Parameters
Danfoss
80G8271.01
10 V
Analog Input Signal
Voltage signal
Current signal
Analog Input Signal
Valve Opening
Degree %
0 V
100% OD
0% OD
20 mA4 mA
Table 21: Driver Mode using analog Signals Parameters
1 = valve Driver, select 1 to operate as valve driver
Driver reference
conguration for 1B, 1D
Driver reference conguration for 1C
0 = Voltage to OD
3 = Current to OD
If I091 or I033 = 0,
dene min reference voltage
If I091 or I033 = 0,
dene max reference voltage
If I033 = 3,
dene min reference current
If I033 = 3,
dene max reference current
WARNING:
EKE 1A can implement Voltage to OD only
6.1.2 Driver Mode using Communication Bus
Driver Mode using Communication Bus
The opening degree of a stepper valve can be operated manually between 0% and 100% OD via communication
bus.
Superheat controller, Type EKE 1A, 1B, 1C, 1D
© Danfoss | Climate Solutions | 2022.06 BC398828796060en-000101 | 40