Table 52: Common Valve parameters (For Danfoss/Non-Danfoss valves)
For some application, it is required that the valve remains open after the control-
ler is o. This parameter denes that OD in %.
NOTE:
This parameter requires connecting a Battery Backup
The Overdrive happens only after Exceeding Override Enable OD.
To limit how frequent overdrive can performed the parameter [I074 - Overdrive
block time] denes the minimum time between 2 overdrive actions. The default
value is 10 minutes
Danfoss
80G8350.10
Actual opening degree
No overdrive
No overdrive
Overdrive
Overdrive
1073
Override
Enabled OD
1074 - Override Block Time
The DI can be used to force the valve to go to this opening degree.
EKE controller has a complex algorithm implemented to handle oscillation issues
related to output valve OD by dening some neutral zone. In neutral zone, the
valve will not move until it overcomes the denite variation in the valve opening
degree.
The benet of using such techniques will not aect the performance of the sys-
tem but will reduce the problem related with the uctuating signal, step loss and
hysteresis in the valve.
NOTE:
Failsafe Position: During failsafe mode of operation (e.g., SH control sensor error or Thermostat sensor error) the
valve position can be set to full close, xed opening degree or average calculated OD. For detail check section
Failsafe operation and parameter list under section control advance sub section Diagnostic SH and Emergency
cooling.
6.3.5 Adding user Dened Refrigerant
Most of the used common Refrigerants have been dened as a pre selectable prole under “Refrigerant list para
O030”. for unlisted refrigerants, user dened refrigerants can be used.
Table 53: Adding user dened refrigerants
13 = R User. to select user
dened refrigerant
Antoine Constant A1 for the user
dened refrigerant. Available only if O030 is on R user option.
Antoine Constant A2 for the user
dened refrigerant. Available only if O030 is on R user option.
Antoine Constant A3 for the user
dened refrigerant. Available only if O030 is on R user option.
Superheat controller, Type EKE 1A, 1B, 1C, 1D