Table 51: Parameters Non-Danfoss valves: for Danfoss vales these parameters are precongured, if the user decides to use a
valve from a dierent manufacturer, then these parameters must be provided by the user.
Parameter
Function
Description
I027
Valve Motor Type
Dene a type of motor used in the stepper valve (Unipolar/Bipolar).
I028
Valve drive current
Setting the Peak current requirement of the motor in mA.
NOTE:
Please be aware that this value must be set in a Peak value. Some valve manufacturers are
using RMS current (1mA RMS = 1.41mA Peak).
I029
Valve step positioning
Denes which position step the valve motor should stop, while changing the opening degree
of the valve.
Choose between:
Full-step
Half-step
Auto - controller will automatically choose based on the valve type right arrow Half step if
Unipolar valve |Full step whereas Bipolar valves
I030
Valve Total Steps
The number of steps that correspond to a valve position of 100%. The total no of steps will
vary according to the selected Valve motor type. For example: ETS 6 has total number of 480
half steps on driving with half phase excitation whereas only 240 full steps on driving with
Full phase excitation.
I031
Valve speed
The desired valve drive rate in steps per second.
NOTE:
Higher valve speed will produce a lower torque. If the valve is used in system having high
dierential pressure, it is better to operate the valve with lower step rate
I032
Valve start speed
Valve initial speed as % of the valve speed (I031). The parameter Is used to avoid high acceler-
ation rate of the stepper motor.
NOTE:
Make sure to select a start speed which is recommended for the used valve.
I061
Valve emergency speed
During power failure conditions, the valve can be driven at higher speed when required to
close faster. To run this feature, it is required to connect EKE with backup battery.
I062
Valve acceleration current
To control the torque in the start and stop sequence, the unit is % of the normal valve driving
current I028 (I031). Note that the torque of the motor is directly proportional to the supplied
current
NOTE:
Make sure not to exceed the rated current of the valve motor, because this might damage it.
I063
Valve Acceleration Time
Denes the time of the acceleration/ deacceleration in the start/stop of the motor.
I077
Holding Current
For some valves, this represents the percent of the programmed Max Phase Current that
should be applied to each phase of the stepper motor to maintain the valve at its last pro-
grammed position. Not all valve designs require a holding current, make sure to check this
with your valve manufacturer
I064
Valve step Mode
Stepper motor can be driven with various step excitation method, which depends valve re-
quirements as well as operating conditions of an application.
The user can choose
Full stepping 1/1
Half stepping 1/2
Micro-stepping (1/4, 1/8, 1/16)
NOTE:
For half and micro stepping, the risk of step loss is higher because the torque provided is low-
er
Danfoss recommends using 1/8 stepping mode as this provides a good balance between tor-
que, speed, and smooth operation.
I065
Valve duty cycle
Denes the valve motion and stop time in a window of 60 seconds.
I070
Start Backlash
The parameter denes the operation of the start backlash function. The valve will normally
open from this point onwards.
I071
Start backslash
The number of steps needed to correct for mechanical hysteresis when a reduction gear is
part of the valve design.
I072
Overdrive
The extra steps taken to secure the closure of the valve.it is dened as a percentage of the full
opening.
I076
Valve Excitation Time After Stop
The time that the drive current is applied after the motor has stopped before going to hold-
ing current. This will make sure that the valve has achieved the nal position before going to
holding current.
© Danfoss | Climate Solutions | 2022.06 BC398828796060en-000101 | 59
Superheat controller, Type EKE 1A, 1B, 1C, 1D

Other manuals for Danfoss EKE 1A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss EKE 1A and is the answer not in the manual?

Danfoss EKE 1A Specifications

General IconGeneral
BrandDanfoss
ModelEKE 1A
CategoryController
LanguageEnglish

Related product manuals