Figure 64: Delta Temperature Reference
Danfos
s
80G354.10
In this mode the response of the controller is quicker in case of load changes.
Table 27: Delta Temperature Reference
Parameter
Function
Description
R102
Operation mode
0 = SH Control
N021
SH reference mode
3 =Delta temp
N009
SH max. value
Maximum allowed SH reference in the range.
N010
SH min. value
Minimum allowed SH reference in the range.
Note: Value must be >0.5K higher than SH close value, if N117=1
N116
SH ref. delta temp factor
Note: this value should be between 0.4 and 0.1. Lower value may ood the
compressor whereas higher values will result in low eciency
N117
SH close function
0 = O | 1 = On, default = 1
N119
SH close setpoint
It is recommended to set the SH close setpoint 2k below the minimum SH.
Default value =2 K (recommended).
I082
S2 sensor conguration
-Selection of the used evaporator temperature sensor S2
I086
Pe transmitter conguration
-Selection of the used evaporator pressure sensor Po
I041
S3 Temperature sensor
-Selection of the used Media temperature S3
6.2.2 Temperature Control Parameters
EKE has 2 methods of controlling the superheat while considering the temperature of the incoming media (using
temperature sensor S3) or based on the outgoing media (using temperature sensor S4).
The 2 methods are:
ON/OFF thermostat.
Modulating thermostat (MTR).
Figure 65: Temperature Control Parameters
EKE
1A
1B
1C
1D
Applicable
-
These modes require one extra temperature sensor S3 or S4, the user can select only one sensor not both.
WARNING:
Superheat control with Thermostatic Mode is not available on EKE 1A.
ON/OFF thermostat
In this mode, if temperature is above the set point + dierential cooling is started with maximum cooling capacity.
In maximum capacity superheat is controlled to be on superheat set point. Cooling is active until the temperature is
below set point. In a startup, cooling will be active if temperature is above temperature set point.
© Danfoss | Climate Solutions | 2022.06 BC398828796060en-000101 | 45
Superheat controller, Type EKE 1A, 1B, 1C, 1D

Other manuals for Danfoss EKE 1A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss EKE 1A and is the answer not in the manual?

Danfoss EKE 1A Specifications

General IconGeneral
BrandDanfoss
ModelEKE 1A
CategoryController
LanguageEnglish

Related product manuals