Figure 61: Load AP
Figure 62: Load AP parameters
Danfoss
84B1489.10
100 %
Superheat
Qo
Uns
t
a
b
le
r
eg
io
n
(wet
)
Min. SH Max. SH
10 %
90 %
Stable
r
egio
n
(
d
r
y
)
Table 26: Load AP parameter
SH max. denes the reference for OD between 90-100% SH max.
must be greater than or equal to SH min.
SH min denes the SH reference for OD between 0 and 10 %.
Note: SH min. value must be >0.5K higher than SH close value, if
N117=1
0 = O | 1 = On, default = 1
It is recommended to set the SH close setpoint 2k below the
minimum SH.
Default value =2 K (recommended).
-Selection of the used evaporator temperature sensor S2
Pe transmitter conguration
-Selection of the used evaporator pressure sensor Po
-Selection of the used Media temperature S3
Delta Temperature Reference
Figure 63: Delta Temperature Reference
In delta temperature, the reference is calculated using evaporator pressure Po and Media temperature S3. It is based
on the fact that most evaporators have a good eciency if the SH reference is set to be 0.65 multiplied by
temperature dierence from inlet temperature to evaporating temperature. The temperature dierence is
calculated as follows SH = Delta temp factor * (S3-T0).
T0: temperature corresponding to evaporator pressure Po
S3: Media temperature
Superheat controller, Type EKE 1A, 1B, 1C, 1D