Figure 59: Minimum Stable Superheat (MSS)
Figure 60: Minimum stable Superheat
Danf
os
s
84B1487.10
100 %
10 %
40 %
Superheat
Qo
Unstable region
(wet
)
Stable
region (d
ry
)
Min. SH Max. SH
Danfoss MSS
It is recommended to set the SH close setpoint 2k below the minimum SH.
Default value =2 K (recommended).
-Selection of the used evaporator temperature sensor S2
Pe transmitter conguration
-Selection of the used evaporator pressure sensor Po
Minimum Stable Superheat (MSS)
The controller will be searching for the minimum stable superheat between an upper and lower boundary specied
by the user. Then if the superheat is stable at a certain value, the controller decreases the superheat reference, if the
SH gets unstable, the SH reference is raised again.
The goal of this method is to search for the lowest possible superheat that can be obtained while still maintaining a
stable system.
Table 25: MSS parameters
Maximum allowed SH reference in the range.
Minimum allowed SH reference in the range.
The amount of allowed uctuation in the superheat before the reference is changed (the range at which the SH
is considered stable)
T0 variant factor (Value from 0 to
1)
Denes how Pressure variation (From Pe) inuence the SH reference.
Safety feature to prevent the ooding of the liquid into the compressor. When the measured superheat goes
bellow the SH close setpoint (parameter N119) 0 = O | 1 = On, default = 1
It is recommended to set the SH close setpoint 2k below the minimum SH.
Default value =2 K (recommended).
-Selection of the used evaporator temperature sensor S2
Pe transmitter conguration
-Selection of the used evaporator pressure sensor Po
Load AP
In Load ap application, SH reference follows a dened curve as shown in the diagram. This two-point curve is
dened by SH max and SH min. These two values must be selected in such a way that the curve is situated between
the MSS curve and the curve for average temperature dierence ΔTm (temperature dierence between media
temperature and evaporating temperature). This makes the regulation more stable compare to MSS because it does
not seek a usability.
WARNING:
Besides the Temperature Sensor S2 and pressure sensor Pe, in this mode a third temperature sensor is needed S3.
© Danfoss | Climate Solutions | 2022.06 BC398828796060en-000101 | 43
Superheat controller, Type EKE 1A, 1B, 1C, 1D