EasyManuals Logo
Home>Danfoss>Controller>EKE 1A

Danfoss EKE 1A User Manual

Danfoss EKE 1A
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #72 background imageLoading...
Page #72 background image
A B
Danfoss
80G8339
A
B
Two status LEDs to indicate operational status
Steady green = power ON
Flashing green = data transmission /
initialization
Flickering red = alarm / error condition
Two status LEDs to indicate valve operation
Flashing red = valve closing
Steady red = valve fully closed
Flashing green = valve opening
Steady green = valve fully open
Both green and red ashing = valve-related
alarm
8 Alarms and troubleshooting
Depending on the application, the EKE 1x series implements error codes and alarms to help the user troubleshoot
and correct parameters easily. When an alarm occurs, the following actions generally ensue:
the “Alarm” or “Warning” relay is activated
an icon and the alarm code are displayed on the screen
The alarms are reset automatically. The alarm is deactivated as soon as the alarm condition ceases. Otherwise, the
user must follow the deactivation procedure once the alarm conditions is over. When the alarm is eliminated the
alarm, relay is deactivated, and the alarm code will no longer be displayed.
Figure 85: LED indication
8.1 Alarms
8.1.1 Conguration errors
Table 55: Conguration errors
Label
Alarm description
Actions during ac‐
tive
Trigger (how the alarm IS
raised)
How to clear the alarm
Remark
E101
Conguration
error
Auto operation
blocked
Active when: - D12 and D13
have the same mapping cong-
uration. - All and AI5 have the
same mapping conguration.
Correct application settings
One or more
conguration errors is block-
ing operation to start. Check the other ac-
tive alarms to identify the conguration
problem.
E011
No refrigerant selec-
ted
Auto operation
blocked
0030 refrigerant set to none
Set 0030 refrigerant set to an
actual refrigerant
No refrigerant is selected,
congure the
correct refrigerant. See "0030 Refrigerant"
E104
SH reference too
close to SH close set
point
Auto operation
blocked
SH close is used and SH close
set pint is too close the actual
reference/ reference minimum
Disable SH close or correct the
actual SH reference / reference
minimum to have 0.5K dier-
ence to SH close set point
SH reference can come to close to the SH
close safety functions et point. which can
result in unstable operation. Keep min.
0.5K separation between minimum SH ref-
erence and N119 SH close set point.
E105
LOP set point too
close to MOP set
point
Auto operation
blocked
If MOP and LOP is used, Mop
set point - Lop set point must >
5K
Disable MOP or LOP, or adjust
the dierence on MOP-LOP set
point >= 5K
The set point for the 2-pressure safety
function Lop and Mop is to close. Keep
min. 5K separation between NO11 MOP
set point and N140 LOP set point
E129
No sensor
cong-
ured for S4
Auto operation
blocked
Application need a S4 signal for
either thermostat or Min S4.
but S4 signal is congured
Disable the functions needing
S4 or congure a S4 signal
Operation is
congured to use S4 (media
out) sensor, but no S4 sensor is congured.
Correct I020 All conguration or AI5 con-
guration and check I042 S4 sensor cong-
uration
E106
No sensor
cong-
ured for S3
Auto operation
blocked
Thermostat need a S3 signal
and no s3 signal is congured
Disable the functions needing
S4 or congure a S4 signal
Operation is
congured to use S3 (media
in) sensor, but no S3 sensor is congured,
Correct 1020 All conguration or AI5 con-
guration and check I041 S3 sensor cong-
uration
Superheat controller, Type EKE 1A, 1B, 1C, 1D
© Danfoss | Climate Solutions | 2022.06 BC398828796060en-000101 | 72

Other manuals for Danfoss EKE 1A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss EKE 1A and is the answer not in the manual?

Danfoss EKE 1A Specifications

General IconGeneral
BrandDanfoss
ModelEKE 1A
CategoryController
LanguageEnglish

Related product manuals