1.
2.
Table 47: Manual control of Relay:
Parameter
Function
Description
O018
Manual mode
1 = On
B101
Manual mode timeout
time in sec. When timed out the parameter [O018 - Manual Mode] will be set to of
B103
Manual relay DO1
0 = O | 1 = ON
When DI2 /DI 3 is congured as Preset OD, the valve OD will be positioned as dened by valve OD parameter [I078 -
Preset OD].
Table 48: Manual Control Valve:
Parameter
Function
Description
O018
Manual mode
1 = On
B101
Manual mode timeout
time in sec. When timed out the parameter [O018 - Manual Mode] will be set to O
O045
Manual OD
Set desired OD in Percentage %
Used to calibrate the valve at Zero OD %. When the user set the manual homing, a full closing operation will be
performed (same as initial closing). After the operation is performed the manual homing parameter [B104 - Manual
Homing] will be set back to o and the parameter for [O045 Manual OD] will be set to 0%. When manual mode
becomes inactive the actual OD will be the starting point for automatic control
Table 49: Manual Homing:
Parameter
Function
Description
O018
Manual mode
1 = On
B101
Manual mode timeout
time in sec. When timed out the parameter [O018 - Manual Mode] will be set to O
O045
Manual OD
Set desired OD in Percentage %
Figure 84: Switching between Auto and manual mode
Danfoss
80G301.10
Manual mode ON
Auto control
Auto control
Valve OD
Time
6.3.4 Valve conguration
Table 50: Valve Conguration
Parameter
Function
Description
I067
Valve Conguration
Danfoss stepper motor are easily selected from Valve
conguration list. On selecting the valve, the
controller will automatically load pre-dened default values. The user is not required to set other
stepper motor parameters for a selected valve from the valve conguration list.
NOTE:
I028 parameter (Valve drive current) needs to be adjusted if the chosen cable length is between
15 and 30m, refer to the installation section
I067
User Dened valve
If a valve from other manufacturers is used, such valve can be
dened as
Set I067 to ‘’User dened Valve’
Enter the Valve parameters (Parameters described below).
Superheat controller, Type EKE 1A, 1B, 1C, 1D
© Danfoss | Climate Solutions | 2022.06 BC398828796060en-000101 | 58