PVEP control specification (continued)
Description Type Value
PWM Control range 10 – 80 %
Float position control PWM_A = PWM_B = 90 %
Frequency 100 -1000 Hz
Input voltage swing 0 UDC
Trigger point 70 % of V bat
Input Impedance Standard pull down 5 kW
Power consumption 7 W
Error voltage Fault V bat
No fault < 2 V
All connector terminals are short-circuit protected, and protected against reverse connection (and their
combinations). Connecting error pins from two or more PVE’s will cause the surveillance system to
malfunction.
PVEP operating conditions
Description Type Value
Pilot Pressure Nominal 13.5 bar [196 psi]
Minimum 10.0 bar [145 psi]
Maximum 15.0 bar [218 psi]
Oil Consumption Neutral 0.04 l/min [0.01 US gal/min]
Locked Position 0.1 l/min [0.03 US gal/min]
Actuating 0.6 l/min [0.16 US gal/min]
Storage Temperature Ambient -40 to +90°C [-40 to +194°F]
Operating Temperature Ambient -30 to +60°C [-22 to +140°F]
Oil Viscosity Operating Range 12 – 75 cSt [65 – 347 SUS]
Minimum 4 cSt [39 SUS]
Maximum 460 cSt [2128 SUS]
Oil Cleanliness Maximum 18/16/13 (according to ISO 4406)
PVEP LED characteristics
Green Operating
Red Internal fault
Red @ 1.5 Hz External or float fault
Service and Parts Manual
PVG 16/32/128/256
Installation
©
Danfoss | October 2018 AX284661889190en-000101 | 31

Table of Contents

Other manuals for Danfoss PVG 128

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss PVG 128 and is the answer not in the manual?

Danfoss PVG 128 Specifications

General IconGeneral
BrandDanfoss
ModelPVG 128
CategoryControl Unit
LanguageEnglish

Related product manuals