The following must be programmed in order shown - see explanation of settings in the Operating Instructions:
Function:
Parameter no. Setting Data value no.
Activation of process controller 100
Speed control, closed loop
[1]
Feedback signal 314
Feedback signal
[2]
Terminal 32 306 Encoder feedback, input B [24]
Terminal 33 307 Encoder feedback, input A [25]
Minimum feedback 414 0 rpm
Maximum feedback 415 1650 rpm (max. ref. + 10%)
Reference 308
Reference (factory setting)
[1]
Terminal 53, min. scale 309 0 Volt (factory setting)
Terminal 53, max. scale 310 10 Volt (factory setting)
Minimum reference 204 0 rpm
Maximum reference 205 1500 rpm
Min. speed 201 0 Hz
Max. speed 202 75 Hz
Proportional gain 417
Application-dependent
Integration time 418
Application-dependent
Differentiation time 419
Application-dependent
VLT
®
5000 Design Guide
108 MG.52.B2.02 - VLT
®
is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss VLT 5000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5000 Series and is the answer not in the manual?

Danfoss VLT 5000 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5000 Series
CategoryDC Drives
LanguageEnglish

Related product manuals