Line reactors for load sharing applications
Line reactors are used when connecting frequency
converters together in a load sharing application.
200 - 240 V units
VLT
type
Nominal
power at CT
Input
current
Voltage
drop
Inductivity Ordering
number
[kW] [A] [%] [mH]
5001 0.75 3.4 1.7 1.934 175U0021
5002 1.10 4.8 1.7 1.387 175U0024
5003 1.50 7.1 1.7 1.050 175U0025
5004 2.20 9.5 1.7 0.808 175U0026
5005 3.0 11.5 1.7 0.603 175U0028
5006 4.0 14.5 1.7 0.490 175U0029
5008 5.5 32.0 1.7 0.230 175U0030
5011 7.5 46.0 1.7 0.167 175U0032
5016 11.0 61.0 1.7 0.123 175U0034
5022 15.0 73.0 1.7 0.102 175U0036
5027 18.5 88.0 1.7 0.083 175U0047
380 - 500 V units
VLT
type
Nominal
power at CT
Input
current
Voltage
drop
Inductivity Ordering
number
[kW] [A] [%] [mH]
5001 0.75 2.3 1 3.196 175U0015
5002 1.1 2.6 1 2.827 175U0017
5003 1.5 3.8 1 1.934 175U0021
5004 2.2 5.3 1 1.387 175U0024
5005 3 7.0 1 1.050 175U0025
5006 4 9.1 1 0.808 175U0026
5008 5.5 12.2 1 0.603 175U0028
5011 7.5 15.0 1 0.490 175U0029
5016 11 32.0 1 0.230 175U0030
5022 15 37.5 1 0.196 175U0031
5027 18.5 44.0 1 0.167 175U0032
5032 22 60.0 1 0.123 175U0034
5042 30 72.0 1 0.102 175U0036
5052 37 89.0 1 0.083 175U0047
5062 45 104.0 1 0.070 175U1009
5072 55 144.6 1 0.051 175U0070
5102 75 174.1 1 0.042 175U0071
See also instruction MI.50.NX.YY for further information.
VLT
®
5000 Design Guide