Required compliance levels
Standard / environment Housing, trades and light industries Industrial environment
Conducted Radiated Conducted Radiated
EN 61000-6-3 (generic) Class B Class B
EN 61000-6-4 Class A-1 Class A-1
EN 61800-3 (restricted) Class A-1 Class A-1 Class A-1 Class A-1
EN 61800-3 (unrestricted) Class B Class B Class A-2 Class A-2
EN 55011: Threshold values and measuring methods for
radio interference from industrial, scientific and
medical (ISM) high-frequency equipment.
Class A-1: Equipment used in a industrial environment.
Unrestricted distribution.
Class A-2: Equipment used in an industrial environment.
Restricted distribution.
Class B: Equipment used in areas with a public supply
network (dwellings, commerce and light indus-
tries). Unrestricted distribution.
EMC Immunity
In order to document immunity against electrical inter-
ference from electrical phenomena, the following im-
munity tests have been made on a system consisting
of a frequency converter (with options, if relevant), a
screened control cable and a control box with potenti-
ometer, motor cable, and motor.
The tests were performed in accordance with the fol-
lowing basic standards:
EN 61000-4-2 (IEC 61000-4-2): Electrostat-
ic discharges (ESD)Simulation of electro-
static discharges from human beings.
EN 61000-4-3 (IEC 61000-4-3): Incoming
electromagnetic field radiation, amplitude
modulatedSimulation of the effects of radar
and radio communication equipment as well
as mobile communications.
EN 61000-4-4 (IEC 61000-4-4): Burst tran-
sients Simulation of interference brought
about by switching with a contactor, relays or
similar devices.
EN 61000-4-5 (IEC 61000-4-5): Surge tran-
sients Simulation of transients brouht e.g. by
lightning that strikes near installations.
VDE 0160 class W2 test pulse: Mains tran-
sients Simulation of high-energy transients
brought about by main fuse breakage,
switching of power factor correction capaci-
tors, etc.
EN 61000-4-6 (IEC 61000-4-6): RF Com-
mon mode Simulation of the effect from ra-
dio-transmitting equipment connected to
connection cables.
See following EMC immunity form.
VLT
®
5000 Design Guide
MG.52.B2.02 - VLT
®
is a registered Danfoss trademark 125
Special conditions

Table of Contents

Other manuals for Danfoss VLT 5000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5000 Series and is the answer not in the manual?

Danfoss VLT 5000 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5000 Series
CategoryDC Drives
LanguageEnglish

Related product manuals