Warning against unintended start
1. The motor can be brought to a stop by means
of digital commands, bus commands, refer-
ences or a local stop, while the frequency
converter is connected to mains.
If personal safety considerations make it nec-
essary to ensure that no unintended start
occurs,
these stop functions are not suffi-
cient.
2. While parameters are being changed, the
motor may start. Consequently,
the stop key
[STOP/RESET] must always be activated,
following which data can be modified.
3. A motor that has been stopped may start if
faults occur in the electronics of the frequen-
cy converter, or if a temporary overload or a
fault in the supply mains or the motor con-
nection ceases.
Use on isolated mains
See section RFI Switch regarding use on isolated
mains.
It is important to follow the recommendations regard-
ing installation on IT-mains, since sufficient protection
of the complete installation must be observed. Not tak-
ing care using relevant monitoring devices for IT-
mains may result in damage.
Warning:
Touching the electrical parts may be fatal - even after the equipment has been disconnected from mains.
Also make sure that other voltage inputs have been disconnected, such as external 24 V DC, load-sharing (linkage
of DC intermediate circuit), as well as the motor connection for kinetic back-up.
VLT 5001 - 5006, 200-240 V: wait at least 4 minutes
VLT 5008 - 5052, 200-240 V: wait at least 15 minutes
VLT 5001 - 5006, 380-500 V: wait at least 4 minutes
VLT 5008 - 5062, 380-500 V: wait at least 15 minutes
VLT 5072 - 5302, 380-500 V: wait at least 20 minutes
VLT 5352 - 5552, 380-500 V: wait at least 40 minutes
VLT 5001 - 5005, 525-600 V wait at least 4 minutes
VLT 5006 - 5022, 525-600 V: wait at least 15 minutes
VLT 5027 - 5062, 525-600 V: wait at least 30 minutes
VLT 5042 - 5352, 525-690 V: wait at least 20 minutes
VLT 5402 - 5602, 525-690 V: wait at least 30 minutes
VLT
®
5000 Design Guide
MG.52.B2.02 - VLT
®
is a registered Danfoss trademark 5
Introduction

Table of Contents

Other manuals for Danfoss VLT 5000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5000 Series and is the answer not in the manual?

Danfoss VLT 5000 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5000 Series
CategoryDC Drives
LanguageEnglish

Related product manuals