Compact, Mains supply 3 x 525 - 690 V
According to international requirements VLT type 5402 5502 5602
Normal overload current (110 %):
Output current
I
VLT,N
[A] (525-550 V)
523 596 630
I
VLT, MAX
(60 s) [A] (525-550 V)
575 656 693
I
VLT,N
[A] (551-690 V)
500 570 630
I
VLT, MAX
(60 s) [A] (551-690 V)
550 627 693
Output S
VLT,N
[kVA] (550 V)
498 568 600
S
VLT,N
[kVA] (575 V)
498 568 627
S
VLT,N
[kVA] (690 V)
598 681 753
Typical shaft output
[kW] (550 V) 400 450 500
[HP] (575 V)
500 600 650
[kW] (690 V) 500 560 630
High overload torque (160 %):
Output current
I
VLT,N
[A] (525-550 V)
429 523 596
I
VLT, MAX
(60 s) [A] (525-550 V)
644 785 894
I
VLT,N
[A] (551-690 V)
410 500 570
I
VLT, MAX
(60 s) [A] (551-690 V)
615 750 855
Output S
VLT,N
[kVA] (550 V)
409 498 568
S
VLT,N
[kVA] (575 V)
408 498 568
S
VLT,N
[kVA] (690 V)
490 598 681
Typical shaft output [kW] (550 V) 315 400 450
[HP] (575 V)
400 500 600
[kW] (690 V) 400 500 560
Max. cable cross-section to
motor and loadsharing
[mm
2
]
4,6
[AWG]
2,4,6
4x240
4x500 mcm
Max. cable cross-section
to brake
[mm
2
]
4,6
[AWG]
2,4,6
2x185
2x350 mcm
Normal overload current (110 %):
Rated input current
I
L,N
[A] (525-550 V)
504 574 607
I
L,N
[A] (551-690 V)
482 549 607
High overload torque (160 %):
Rated input current
I
L,N
[A] (525-550 V)
413 504 574
I
L,N
[A] (551-690 V)
395 482 549
Max. cable cross-section
power supply
[mm
2
]
4,6
[AWG]
2,4,6
4x240
4x500 mcm
Max. pre-fuses (mains) [-]/
UL
[A]
1
700/700 900/900 900/900
Efficiency
3
0,98
Power loss
Normal overload [W]
7249 8727 9673
High overload [W] 5818 7671 8715
Weight
IP 00 [kg]
221 236 277
Weight
IP 21/Nema1 [kg]
263 272 313
Weight
IP 54/Nema12 [kg] 263 272 313
Enclosure IP 00, IP 21/Nema 1 and IP 54/Nema12
1.
For type of fuse see section Fuses
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Max. cable cross-section is the maximum possible cable cross-section allowed to be fitted on the terminals. Always comply with
national and local regulations on min. cable cross-section.
5. Weight without shipping container.
6. Connection bolt power supply, motor and loadsharing: M10 (compression lug), 2xM8 (box lug), M8 (brake)
VLT
®
5000 Design Guide
MG.52.B2.02 - VLT
®
is a registered Danfoss trademark 53
Technical data

Table of Contents

Other manuals for Danfoss VLT 5000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5000 Series and is the answer not in the manual?

Danfoss VLT 5000 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5000 Series
CategoryDC Drives
LanguageEnglish

Related product manuals