Transfer impedance (Z
T
) is rarely stated by cable man-
ufacturers, but it is often possible to estimate transfer
impedance (Z
T
) by assessing the physical design of
the cable.
Transfer impedance (Z
T
) can be assessed on the basis
of the following factors:
-
The conductibility of the screen material.
-
The contact resistance between the individ-
ual screen conductors.
-
The screen coverage, i.e. the physical area
of the cable covered by the screen - often
stated as a percentage value.
-
Screen type, i.e. braided or twisted pattern.
Aluminium-clad with copper wire.
Twisted copper wire or armoured steel wire cable.
Single-layer braided copper wire with varying percentage
screen coverage.
This is the typical Danfoss reference cable.
Double-layer braided copper wire.
Twin layer of braided copper wire with a magnetic, screened/
armoured intermediate layer.
Cable that runs in copper tube or steel tube.
Lead cable with 1.1 mm wall thickness.
VLT
®
5000 Design Guide
MG.52.B2.02 - VLT
®
is a registered Danfoss trademark 79
Electrical installation

Table of Contents

Other manuals for Danfoss VLT 5000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5000 Series and is the answer not in the manual?

Danfoss VLT 5000 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5000 Series
CategoryDC Drives
LanguageEnglish

Related product manuals