Compact, AC line supply 3 x 525-600 V
According to international requirements VLT type 5016 5022 5027
Normal overload torque (110 %):
Output current
I
VLT,N
[A] (550 V)
23 28 34
I
VLT, MAX
(60 s) [A] (550 V)
25
31 37
I
VLT,N
[A] (575 V)
22
27 32
I
VLT, MAX
(60 s) [A] (575 V)
24
30 35
Output
S
VLT,N
[kVA] (550 V)
22 27 32
S
VLT,N
[kVA] (575 V)
22
27 32
Typical shaft output
P
VLT,N
[kW]
15 18.5 22
Typical shaft output
P
VLT,N
[HP]
20 25 30
High overload torque (160 %):
Output current
I
VLT,N
[A] (550 V)
18 23 28
I
VLT, MAX
(60 s) [A] (550 V)
29
37 45
I
VLT,N
[A] (575 V)
17
22 27
I
VLT, MAX
(60 s) [A] (575 V)
27
35 43
Output
S
VLT,N
[kVA] (550 V)
17 22 27
S
VLT,N
[kVA] (575 V)
17
22 27
Typical shaft output
P
VLT,N
[kW]
11 15 18.5
Typical shaft output
P
VLT,N
[HP]
15 20 25
Max. cable cross-section to motor, 16 16 35
brake and load sharing [mm
2
]/[AWG]
2)
6 6 2
Min. cable cross-section to motor, 0.5 0.5 10
brake and load sharing [mm2]/[AWG]
4)
20 20 8
Normal overload torque (110 %):
Rated input current
I
L,N
[A] (550 V)
22 27 33
I
L,N
[A] (600 V)
21 25 30
High overload torque (160 %):
Rated input current
I
L,N
[A] (550 V)
18 22 27
I
L,N
[A] (600 V) 16 21 25
Max. cable cross-section, 16 16 35
power [mm
2
]/[AWG]
2)
6 6 2
Max. pre-fuses
[-]/UL
1)
[A]
30 35 45
Efficiency
3)
0.96 0.96 0.96
Weight IP 20 EB [kg] 23 23 30
Power loss at max. load [W] 576 707 838
Enclosure IP 20/Nema 1
1. For type of fuse, see section Fuses.
2. American Wire Gauge.
3. Measured using 100 ft [30 m] shielded motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals to comply with IP 20. Always comply
with national and local regulations on min. cable cross-section.
VLT
®
5000 Series
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark. 25
Technical data