Compact, AC line supply 3 x 550-600 V
According to international requirements VLT type 5150 5200 5250
Normal overload torque (110 %):
Output current
I
VLT,N
[A] (550 V)
201 253 289
I
VLT, MAX
(60 s) [A] (550 V)
221 278 318
I
VLT,N
[A] (575 V)
192 242 289
I
VLT, MAX
(60 s) [A] (575 V)
211 266 318
Output
S
VLT,N
[kVA] (550 V)
191 241 275
S
VLT,N
[kVA] (575 V)
191 241 288
Typical shaft output P
VLT,N
[kW]
132 160 200
Typical shaft output P
VLT,N
[HP]
200 250 300
High overload torque (160 %):
Output current
I
VLT,N
[A] (550 V)
151 201 253
I
VLT, MAX
(60 s) [A] (550 V)
242 322 405
I
VLT,N
[A] (575V)
144 192 242
I
VLT, MAX
(60 s) [A] (575 V)
230 307 387
Output
S
VLT,N
[kVA] (550 V)
144 191 241
S
VLT,N
[kVA] (575 V)
143 191 241
Typical shaft output P
VLT,N
[kW]
110 132 160
Typical shaft output P
VLT,N
[HP]
150 200 250
Max. cross-section of copper cable to motor, brake
and loads haring [mm
2
]
AWG
2x120
2x4/0
2x120
2x4/0
2x120
2x4/0
Max. cross-section of copper cable to motor, brake
and loads haring [mm
2
]
AWG
2x185
2x300 mcm
2x185
2x300 mcm
2x185
2x300 mcm
Min. cable cross-section to motor, brake and load
sharing
4)
[mm
2
]
AWG
2x6
2x8
2x6
2x8
2x6
2x8
1. For type of fuse, see section Fuses.
2. American Wire Gauge.
3. Measured using 100 ft [30 m] shielded motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals. Always comply
with national and local regulations on min. cable cross-section.
5. Connection stud 1 x M8/2 x M8.
VLT
®
5000 Series
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark. 29
Technical data