Compact, AC line supply 3 x 550-600 V
According to international requirements VLT type 5075 5100 5125
Max input current 110%
I
L,MAX
[A] (550 V)
101 128 147
I
L,MAX
[A] (575 V)
92 117 134
Max input current 160%
I
L,MAX
[A] (550 V)
79 101 128
I
L,MAX
[A] (575 V)
72 92 117
Max. cross-section of copper cable to power [mm
2
]
120 120 120
Max. cross-section of aluminum cable to power [mm
2
]
185 185 185
Max. cross-section of copper cable to power [AWG] 4/0 4/0 4/0
Max. cross-section of aluminum cable to power [AWG] 300 mcm 300 mcm 300 mcm
Min. cable cross-section to motor, brake and load shar-
ing
4)
[mm
2/
AWG]
2) 5)
6/8 6/8 6/8
Max. pre-fuses (line power) [-]/UL
1)
[A]
125 175 200
Integral pre-fuses (softcharge circuit) [-]/UL
6)
[A]
15/15 15/15 15/15
Integral pre-fuses (softcharge resistors) [-]/UL
7)
[A]
12/12 12/12 12/12
Integral pre-fuses (SMPS) [-]/UL
8)
[A]
5 5 5
Efficiency 0.96-0.97
Weight IP 00
[kg] 109 109 109
Weight Nema 1 EB [kg] 121 121 121
Power loss at max. load [W] 2560 3275 3775
Enclosure IP 00/Nema 1 (IP 20)
1. For type of fuse, see section Fuses.
2. American Wire Gauge.
3. Measured using 100 ft [30 m] shielded motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals. Always comply
with national and local regulations on min. cable cross-section.
5. Connection stud 1 x M8/2 x M8.
6. If UL/cUL is to be complied with, AC Littelfuse type KLK, Danfoss ordering no. 176F1147 must be used.
7. If UL/cUL is to be complied with, DC Littelfuse type KLKD, Danfoss ordering no. 176F1192 must be used.
8. If UL/cUL is to be complied with, Bussmann type KTK-5, Danfoss ordering no. 175L3437 must be used.
VLT
®
5000 Series
28 MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.

Table of Contents

Other manuals for Danfoss VLT 5003

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5003 and is the answer not in the manual?

Danfoss VLT 5003 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5003
CategoryDC Drives
LanguageEnglish

Related product manuals