Compact, AC line supply 3 x 550-600 V
According to international requirements VLT type 5075 5100 5125
Normal overload torque (110 %):
Output current
I
VLT,N
[A] (550 V)
104 131 151
I
VLT, MAX
(60 s) [A] (550 V)
114 144 166
I
VLT,N
[A] (575 V)
99 125 144
I
VLT, MAX
(60 s) [A] (575 V)
109 138 158
Output
S
VLT,N
[kVA] (550 V)
99 125 144
S
VLT,N
[kVA] (575 V)
99 124 143
Typical shaft output P
VLT,N
[kW]
75 90 11
Typical shaft output P
VLT,N
[HP]
100 125 150
High overload torque (160 %):
Output current
I
VLT,N
[A] (550 V)
81 104 131
I
VLT, MAX
(60 s) [A] (550 V)
130 166 210
I
VLT,N
[A] (575 V)
77 99 125
I
VLT, MAX
(60 s) [A] (575 V)
123 158 200
Output
S
VLT,N
[kVA] (550 V)
77 99 125
S
VLT,N
[kVA] (575 V)
77 99 124
Typical shaft output (380-440 V) P
VLT,N
[kW]
55 75 90
Typical shaft output (380-440 V) P
VLT,N
[HP]
75 100 125
Max. cross-section of copper cable to motor, brake
and load sharing (380-440 V) [mm
2
]
[AWG]
120
4/0
120
4/0
120
4/0
Max. cross-section of copper cable to motor, brake
and load sharing (441-500 V) [mm
2
]
[AWG]
185
300 mcm
185
300 mcm
185
300 mcm
Min. cable cross-section to motor, brake and load
sharing
4)
[mm
2/
AWG]
6
8
6
8
6
8
1. For type of fuse, see section Fuses.
2. American Wire Gauge.
3. Measured using 100 ft [30 m] shielded motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals. Always comply
with national and local regulations on min. cable cross-section.
5. Connection stud 1 x M8/2 x M8.
VLT
®
5000 Series
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark. 27