VLT
®
6000 HVAC Series
Service functions 600-631
This parameter group contains functions such as
operating data, data log and fault log.
It also has information on the nameplate data
of the frequency converter.
These service functions are very useful in connection
with operating and fault analysis in an installation.
600-605 Operating data
Value:
Parameter
no.
Description
Operating data:
Display text Unit Range
600 Operating hours (OPERATING HOURS) Hours 0 - 130,000.0
601 Hours run (RUNNING HOURS) Hours 0 - 130,000.0
602 kWh counter (KWH COUNTER) kWh -
603 No. of cut-ins (POWER UP‘S) Nos. 0 - 9999
604 No. of overtemps. (OVER TEMP‘S) Nos. 0 - 9999
605 No. of overvoltages (OVER VOLT‘S) Nos. 0 - 9999
Function:
These parameters can be read out via the
serial communication port, as well as via the
display in the parameters.
Description of choice:
Parameter 600 Operating hours:
Gives the number of hours in which the frequency
converter has been in operation. The value is saved
every hour and when the power supply to the unit
is cut off. This value cannot be reset.
Parameter 601 Hours run:
Gives the number of hours in which the motor has
been in operation since being reset in parameter 619
Reset of hours-run counter. The value is saved every
hour and when the power supply to the unit is cut off.
Parameter 602 kWh counter:
Gives the output power of the frequency converter.
The calculation is based on the mean value in
kWh over one hour. This value can be reset using
parameter 618 Reset of kWh counter.
Parameter 603 No. of cut-ins:
Gives the number of cut-ins of supply voltage
to the frequency converter.
Parameter 604 No. of overtemps:
Gives the number of overtemperature errors on the
heat-sink of the frequency converter.
Parameter 605 No. of overvoltages:
Gives the number of overvoltages on the intermediate
circuit voltage of the frequency converter. The count is
onlytakenwhenAlarm7Overvoltage is active.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.61.A5.02 - VLT is a registered Danfoss trademark
130

Table of Contents

Other manuals for Danfoss VLT 6000 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 6000 series and is the answer not in the manual?

Danfoss VLT 6000 series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 6000 series
CategoryMedia Converter
LanguageEnglish

Related product manuals