6000 HVAC Series
Programming
■ Quick Menu
The QUICK MENU key gives access to 12 of the
most important setup parameters of the drive. After
programming, the drive will, in many cases, be ready
for operation. The 12 Quick Menu parameters are
shown in the table below. A complete description
of the function is given in the parameter
sections of this manual.
Quick Menu Parameter Description
Item Number Name
1 001 Language Selects language used for all displays.
2 102 Motor Power Sets output characteristics of drive based on kW size
of motor.
3 103 Motor Voltage Sets output characteristics of drive based on voltage
ofmotor.
4 104 Motor Frequency Sets output characteristics of drive based on nominal
frequency of motor. This is typically equal to line
frequency.
5 105 Motor Current Sets output characteristics of drive based on nominal
current in amps of motor.
6 106 Motor Nominal Speed Sets output characteristics of drive based on nominal
full load speed of motor.
7 201 Minimum Frequency Sets minimum controlled frequency at which motor
will run.
8 202 Maximum Frequency Sets maximum controlled frequency at which motor
will run.
9 206 Ramp Up Time Sets time to accelerate motor from 0 Hz to nominal
motor frequency set in Quick Menu Item 4.
10 207 Ramp Down Time Sets time to decelerate motor from nominal motor
frequency set in Quick Menu Item 4 to 0 Hz.
11 323 Relay1 Function Sets function of high voltage Form C relay.
12 326 Relay 2 Function Sets function of low voltage Form A relay.
MG.61.A5.02 - VLT is a registered Danfoss trademark