Page #151 background image
VLT
®
6000 HVAC Series
All about VLT 6000
HVAC
Acoustic noise
The acoustic interference from the frequency converter comes
from two sources:
1. DC intermediate circuit coils
2. Integral fan.
Below are the typical values measured at a distanceof 1 m from
the unit at full load and are nominal maximum values:
VLT 6002-6006 200-240 V, VLT 6002-6011 380-460 V
IP 20 units: 50 dB(A)
IP 54 units: 62 dB(A)
VLT 6008-6027 200-240 V, VLT 6016-6122 380-460 V
IP 20 units: 61 dB(A)
IP 54 units: 66 dB(A)
VLT 6042-6062 200-240 V
IP 00/20 units: 70 dB(A)
IP 54 units: 65 dB(A)
VLT 6152-6352 380-460 V
IP 00/21/NEMA 1/IP 54: 74 dB(A)
VLT 6402 380-460 V
All enclosure types: 80 dB(A)
VLT 6502-6602 380-460 V
All enclosure types: 83 dB(A)
VLT 6002-6011 525-600 V
IP 20/NEMA 1 units: 62 dB(A)
VLT 6102-6402 525-600 V
IP 20/NEMA 1 units: 74 dB(A)
IP 54 units: 74 dB(A)
VLT 6502 525-600 V
All units: 80 dB(A)
VLT 6602-6652 525-600 V
All units: 83 dB(A)
* Measured 1 meter from the unit at full load.
Derating for ambient temperature
The ambient temperature (T
AMB,MAX
) is the maximum
temperature allowed. The average (T
AMB,AVG
) measured
over 24 hours must be at least 5 ºC lower
.
If VLT 6000 HVAC is operated at temperat
ures
above 45 ºC, a derating of the continuous
output current is necessary.
The current of VLT 6152-6602, 380-460 V and
VLT 6102-6402, 525-600 V, is to be derated
1%/ºC above 40° C to 55ºC maximum.
The current of VLT 6502-6652, 525-600 V, is to be
derated 1.5%/ºC above 40° C to 55ºC maximum.
MG.61.A5.02 - VLT is a registered Danfoss trademark
151

Table of Contents

Other manuals for Danfoss VLT 6000 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 6000 series and is the answer not in the manual?

Danfoss VLT 6000 series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 6000 series
CategoryMedia Converter
LanguageEnglish

Related product manuals