VLT
®
6000 HVAC Series
■ Technical data, mains supply 3 x 200-240V
According to international requirements VLT type 6002 6003 6004 6005 6006 6008 6011
Output current
4)
I
VLT,N
[A] 6.6 7.5 10.6 12.5 16.7 24.2 30.8
I
VLT, MAX
(60 s) [A] 7.3 8.3 11.7 13.8 18.4 26.6 33.9
Output power (240 V) S
VLT,N
[kVA] 2.7 3.1 4.4 5.2 6.9 10.1 12.8
Typical shaft output P
VLT,N
[kW] 1.1 1.5 2.2 3.0 4.0 5.5 7.5
Typical shaft output P
VLT,N
[HP] 1.5 2 3 4 5 7.5 10
Max. cable
cross-section to
motor
and DC-bus
[mm
2
]/[AWG]
4/10 4/10 4/10 4/10 10/8 16/6 16/6
Max. input current
(200 V) (RMS)I
L,N
[A]
6.0 7.0 10.0 12.0 16.0 23.0 30.0
Max. cable
cross-section power
[mm
2
]/[AWG]
2)
4/10 4/10 4/10 4/10 4/10 16/6 16/6
Max. pre-fuses [-]/UL
1)
[A] 16/10 16/15 25/20 25/25 35/30 50 60
Efficiency
3)
0.95 0.95 0.95 0.95 0.95 0.95 0.95
Weight IP 20 [kg] 7 7 9 9 23 23 23
Weight IP 54 [kg] 11.5 11.5 13.5 13.5 35 35 38
Power loss at
max. load. [W]
Total 76 95 126 172 194 426 545
Enclosure VLT type IP 20 / IP 54
1. Fortypeoffuse,seesectionFuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Current ratings fulfill UL requirements for 208-240 V.