Installation
Mains supply (L1, L2, L3)
Mains supply (L1, L2, L3):
Supply voltage 200-240 V units ........................................................................ 3 x 200/208/220/230/240 V ±10%
Supply voltage 380-460 V units ........................................................................ 3 x 380/400/415/440/460 V ±10%
Supply voltage 525-600 V units ............................................................................... 3 x 525/550/575/600 V ±10%
Supply frequency ............................................................................................................................ 48-62 Hz ± 1%
Max. imbalance of supply voltage:
VLT 6002-6011, 380-460 V and 525-600 V and VLT 6002-6005, 200-240 V .......... ±2.0% of rated supply voltage
VLT 6016-6072, 380-460 V and 525-600 V and VLT 6006-6032, 200-240 V .......... ±1.5% of rated supply voltage
VLT 6102-6602, 380-460 V and VLT 6042-6062, 200-240 V .................................. ±3.0% of rated supply voltage
VLT 6102-6652, 525-600 V ....................................................................................... ±3% of rated supply voltage
True Power factor (λ) ...................................................................................................... 0.90 nominal at rated load
Displacement Power Factor (cos. ϕ) ............................................................................................ near unity (>0.98)
No. of switches on supply input L1, L2, L3 .......................................................................... approx. 1 time/2 min.
Max. short-circuit current ....................................................................................................................... 100.000 A
VLT output data (U, V, W):
Output voltage ................................................................................................................ 0-100% of supply voltage
Output frequency:
Output frequency 6002-6032, 200-240V .............................................................................. 0-120 Hz, 0-1000 Hz
Output frequency 6042-6062, 200-240V ................................................................................ 0-120 Hz, 0-450 Hz
Output frequency 6002-6062, 380-460V .............................................................................. 0-120 Hz, 0-1000 Hz
Output frequency 6072-6602, 380-460V ................................................................................ 0-120 Hz, 0-450 Hz
Output frequency 6002-6016, 525-600V .............................................................................. 0-120 Hz, 0-1000 Hz
Output frequency 6022-6062, 525-600V ................................................................................ 0-120 Hz, 0-450 Hz
Output frequency 6072, 525-600V ......................................................................................... 0-120 Hz, 0-450 Hz
Output frequency 6102-6352, 525-600V ................................................................................ 0-132 Hz, 0-200 Hz
Output frequency 6402-6652, 525-600V ................................................................................ 0-132 Hz, 0-150 Hz
Rated motor voltage, 200-240 V units .............................................................................. 200/208/220/230/240V
Rated motor voltage, 380-460 V units .............................................................................. 380/400/415/440/460V
Rated motor voltage, 525-600 V units ............................................................................................ 525/550/575 V
Rated motor frequency ............................................................................................................................ 50/60 Hz
Switching on output ................................................................................................................................. Unlimited
Ramp times ....................................................................................................................................... 1 - 3600 sec.
Torque characteristics:
Starting torque ............................................................................................................................... 110% for 1 min.
Starting torque (parameter 110 High break-away torque) ....................................... Max. torque: 160% for 0.5 sec.
Acceleration torque ....................................................................................................................................... 100%
Overload torque ............................................................................................................................................ 110%
MG.61.A5.02 - VLT is a registered Danfoss trademark
21

Table of Contents

Other manuals for Danfoss VLT 6000 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 6000 series and is the answer not in the manual?

Danfoss VLT 6000 series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 6000 series
CategoryMedia Converter
LanguageEnglish

Related product manuals