VLT
®
6000 HVAC Series
Derating for air pressure
Below 1000 m altitude no derating is necessary.
Above 1000 m the ambient temperature (T
AMB
)or
max. output current (I
VLT,MAX
) must be derated in
accordance with the diagram below:
1. Derating of output current versus altitude
at T
AMB
= max. 45°C
2. Derating of max. T
AMB
versus altitude at
100% output current.
Derating for running at low speed
When a centrifugal pump or a fan is controlled by a VLT
6000 HVAC frequency converter, it is not necessary
to reduce the output current at low speed because
the load characterstic of the centrifugal pumps/fans,
automatically ensures the necessary reduction.
Derating for long motor cables or cables
with larger cross-section
VLT 6000 HVAC has been tested using 300
m unscreened/unarmoured cable and 150 m
screened/armoured cable.
VLT 6000 HVAC has been designed to work using a
motor cable with a rated cross-section. If a cable with
a larger cross-section is to be used, it is recommended
to reduce the output current by 5% for every step
the cross-section is increased. (Increased cable
cross-section leads to increased capacity to earth,
and thus an increased earth leakage current).
Derating for high switching frequency
A higher switching frequency (to be set in parameter
407, Switching frequency) leads to higher losses in
the electronics of the frequency converter.
VLT 6000 HVAC has a pulse pattern in which
it is possible to set the switching frequency
from 3.0- 10.0/14.0 kHz.
The frequency converter will automatically derate
the rated output current I
VLT,N,
when the switching
frequency exceeds 4.5 kHz.
In both cases, the reduction is carried out
linearly, down to 60% of I
VLT,N
.
The table gives the min., max. and factory-set
switching frequencies for VLT 6000 HVAC units.
Switching frequency [kHz] Min. Max. Fact.
VLT 6002-6005, 200 V 3.0 10.0 4.5
VLT 6006-6032, 200 V
3.0 14.0 4.5
VLT 6042-6062, 200 V
3.0 4.5 4.5
VLT 6002-6011, 460 V
3.0 10.0 4.5
VLT 6016-6062, 460 V
3.0 14.0 4.5
VLT 6072-6122, 460 V
3.0 4.5 4.5
VLT 6152-6352, 460 V
3.0 4.5 4.5
VLT 6402-6602, 460 V
1.5 3.0 3.0
VLT 6002-6011, 600 V
4.5 7.0 4.5
VLT 6016-6032, 600 V
3.0 14.0 4.5
VLT 6042-6062, 600 V
3.0 10.0 4.5
VLT 6072, 600 V
3.0 4.5 4.5
VLT 6102-6352, 690 V
1.5 2.0 2.0
VLT 6402-6652, 600 V
1.5 1.5 1.5
MG.61.A5.02 - VLT is a registered Danfoss trademark
152

Table of Contents

Other manuals for Danfoss VLT 6000 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 6000 series and is the answer not in the manual?

Danfoss VLT 6000 series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 6000 series
CategoryMedia Converter
LanguageEnglish

Related product manuals