■ Peak voltage on motor
When a transistor in the inverter is opened,
the voltage across the motor increases by a
dV/dt ratio that depends on:
- the motor cable (type, cross-section, length
screened or unscreened)
- inductance
The natural induction causes an overshot U
PEAK
in the
motor voltage before it stabilises itself at a level which
depends on the voltage in the intermediate circuit. The
rise time and the peak voltage U
PEAK
affect the service
life of the motor. If the peak voltage is too high, motors
without phase coil insulation are the ones that will
primarily be affected. If the motor cable is short (a few
metres),therisetimeandpeakvoltagearelower.
If the motor cable is long (100 m), the rise time
and peak voltage will increase.
If very small motors are used without phase coil
insulation, it is recommended to fit a LC filter
after the frequency converter.
Typical values for the rise time and peak voltage
U
PEAK
are measured on the motor terminals
between two phases.
To obtain approximate values for cable lengths
and voltages not mentioned below, use the
following rules of thumb:
1. Rise time increases/decreases proportionally with
cable length.
2. U
PEAK
= DC link voltage x 1.9
(DC link voltage = Mains voltage x 1.35).
3.
Data are measured according to IEC 60034-17.
VLT 6002-6011 / 380-460 V
Cable
length
Mains
volt-
age Rise time
Peak
voltage dU/dt
50 metres 380 V 0.3 µsec. 850 V 2000 V/µsec.
50 metres 500 V 0.4 µsec. 950 V 2600 V/µsec.
150 metres 380 V 1.2 µsec. 1000 V 667 V/µsec.
150 metres 500 V 1.3 µsec. 1300 V 800 V/µsec.
VLT 6016-6122 / 380-460 V
Cable
lengt
h
Mains
volt-
age Rise t
ime
Peak
volta
ge
dU/dt
32 metres 380 V 0.27 µsec. 950 V 2794 V/µsec.
70 metres 380 V 0.60 µsec. 950 V 1267 V/µsec.
132 me
tres
380 V 1.11 µ
sec.
950 V 685 V/
µsec.
VLT 6152-6352 / 380-460 V
Cable
length
Mains
volt-
age Rise time
Peak
voltage dU/dt
70 metres 400 V 0.34 µsec. 1040 V 2447 V/µsec.
VLT 6402-6602 / 380-460 V
Cable
length
Mains
volt-
age Rise time
Peak
voltage dU/dt
29 metres 500 V 0.71 µsec. 1165 V 1389 V/µsec.
29 metres 400 V 0.61 µsec. 942 V 1233 V/µsec.
VLT 6002-6011 / 525-600 V
Cable
length
Mains
volt-
age Rise time
Peak
voltage dU/dt
35 metres 600 V 0.36 µsec. 1360 V 3022 V/µsec.
VLT 6016-6072 / 525-600 V
Cable
length
Mains
volt-
age Rise time
Peak
voltage dU/dt
35 metres 575 V 0.38 µsec. 1430 V 3011 V/µsec.
VLT 6102-6402 / 525-600 V
Cable
length
Mains
voltage Rise time
Peak
voltage dU/dt
25 metres 575 V 0.45 µsec. 1159 1428 V/µsec.
VLT 6502-6652 / 525-600 V
Cable
length
Mains
voltage Rise time
Peak
voltage dU/dt
25 metres 575 V 0.25 µsec. 1159 2510 V/µsec.
■ Switching on the input
Switching on the input depends on the mains
voltage in question.
The table states the waiting time between cut-ins.
Mains voltage 380 V 415 V 460 V
Waiting time 48 s 65 s 89 s