VLT
®
6000 HVAC Series
PNU Parameter Factory setting Range Changes 4-Setup Conversion Data
# description during operation index type
100 Configuration Open loop No Yes 0 5
101 Torque characteristics Automatic Energy
Optimisation
No Yes 0 5
102 Motor power, P
M,N
Depends on the unit 0.25-500 kW No Yes 1 6
103 Motor voltage, U
M,N
Depends on the unit 200-575 V No Yes 0 6
104 Motor frequency, f
M,N
50 Hz 24-1000 Hz No Yes 0 6
105 Motor current, l
M,N
Depends on the unit 0.01-I
VLT,MAX
No Yes -2 7
106 Rated motor speed, n
M,N
Depends on par. 102 Motor
power
100-60000 rpm No Yes 0 6
107 Automatic motor adaptation, AMA Optimisation disable No No 0 5
108 Start voltage of parallel motors Depends on par. 103 0.0 - par. 103 Yes Yes -1 6
109 Resonance dampening 100 % 0 - 500 % Yes Yes 0 6
110 High break-away torque OFF 0.0 - 0.5 sec. Yes Yes -1 5
111 Start delay 0.0 sec. 0.0 - 120.0 sec. Yes Yes -1 6
112 Motor preheater Disable Yes Yes 0 5
113 Motor preheater DC current 50 % 0 - 100 % Yes Yes 0 6
114 DC braking current 50 % 0 - 100 % Yes Yes 0 6
115 DC braking time 10 sec. 0.0 - 60.0 sec. Yes Yes -1 6
116 DC brake cut-in frequency OFF 0.0-par. 202 Yes Yes -1 6
117 Motor thermal proctection ETR Trip 1 Yes Yes 0 5
118 Motor power factor 0.75 0.50 - 0.99 No Yes -2 6
MG.61.A5.02 - VLT is a registered Danfoss trademark
162