VLT
®
6000 HVAC Series
Single-pole start/stop
- Start/stop using terminal 18.
Parameter 302 = Start [1]
- Quick-stop using terminal 27.
Parameter 304 = Coasting stop, inverse [0]
Digital speed up/down
- Speed up and down using terminals 32 and 33.
Parameter 306 = Speed up [7]
Parameter 307 = Speed down [7]
Parameter 305 = Freeze reference [2]
Potentiometer reference
-Parameter 308 = Reference [1]
Parameter 309 = Terminal 53, min. scaling
Parameter 310 = Terminal 53, max. scaling
Run permissive
- Start permitted with terminal 16.
Parameter 300 = Run permissive [8]
- Start/stop with terminal 18.
Parameter 302 = Start [1]
- Quickstop with terminal 27.
Parameter 304 = Coasting stop, inverse [0].
- Activated damper (motor)
Parameter 323 = Start command active [13].
2-zone regulation
- Parameter 308 = Feedback [2].
- Parameter 311 = Feedback [2].
Transmitter connection
- Parameter 314 = Reference [1]
- Parameter 315 = Terminal 60, min. scaling
- Parameter 316 = Terminal 60, max. scaling
MG.61.A5.02 - VLT is a registered Danfoss trademark
70

Table of Contents

Other manuals for Danfoss VLT 6000 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 6000 series and is the answer not in the manual?

Danfoss VLT 6000 series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 6000 series
CategoryMedia Converter
LanguageEnglish

Related product manuals