7.1.3
VLT
®
AutomationDrive FC 302
Power range N250 N315 N355 N400 N450
Drive modules 2 2 2 2 2
Rectier conguration 12-pulse 6-pulse/12-pulse
High/normal load HO NO HO NO HO NO HO NO HO NO
Typical shaft output at 400 V [kW] 250 315 315 355 355 400 400 450 450 500
Typical shaft output at 460 V [hp] 350 450 450 500 500 600 550 600 600 650
Typical shaft output at 500 V [kW] 315 355 355 400 400 500 500 530 530 560
Protection rating IP00
Eciency 0.98
Output frequency [Hz] 0–590
Heat sink overtemperature trip
[°C (°F)]
110 (230)
Power card ambient trip [°C (°F)]
80 (176)
Output current [A]
Continuous (at 380–440 V) 480 588 600 658 658 745 695 800 810 880
Intermittent (60 s overload) at 400 V 720 647 900 724 987 820 1043 880 1215 968
Continuous (at 460/500 V) 443 535 540 590 590 678 678 730 730 780
Intermittent (60 s overload) at
460/500 V
665 588 810 649 885 746 1017 803 1095 858
Continuous (at 400 V) [kVA] 333 407 416 456 456 516 482 554 554 610
Continuous (at 460 V) [kVA] 353 426 430 470 470 540 540 582 582 621
Continuous (at 500 V) [kVA] 384 463 468 511 511 587 587 632 632 675
Input current [A]
Continuous (at 400 V) 463 567 590 647 647 733 684 787 779 857
Continuous (at 460/500 V) 427 516 531 580 580 667 667 718 711 759
Power losses [W]
Drive modules at 400 V 4505 5825 5502 6110 6110 7069 6375 7538 7526 8468
Drive modules at 460 V 4063 4998 5384 5964 5721 6175 6070 6609 6604 7140
AC busbars at 400 V 545 550 551 555 555 561 557 565 566 575
AC busbars at 460 V 543 548 548 551 556 556 556 560 560 563
Maximum cable size [mm
2
(mcm)]
Mains
1)
4x120 (250) 4x150 (300)
Motor 4x120 (250) 4x150 (300)
Brake 4x70 (2/0) 4x95 (3/0)
Regeneration terminals 4x120 (250) 4x150 (300) 6x120 (250)
Maximum external mains fuses
6-pulse conguration 600 V, 1600 A
12-pulse conguration 600 V, 700 A 600 V, 900 A
Table 7.10 FC 302, 380–500 V AC Mains Supply (2-module System)
1) For 12-pulse units, the cables between the star and delta terminals must be equal in number and length.
Specications User Guide
MG37L202 Danfoss A/S © 08/2017 All rights reserved. 63
7 7

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals