7.3.2.2 Recommended Fuses for UL Compliance
•
The drive modules are supplied with built-in AC fuses. The modules have been qualied for 100 kA short circuit
current rating (SCCR) for the standard busbar congurations at all voltages (380–690 V AC).
•
The drive system is qualied for 100 kA SCCR with any Class L or Class T UL-listed fuses connected at the input
terminals of the drive modules, if no power options or extra busbars are connected externally.
•
The current rating of the Class L or Class T fuses should not exceed the listed fuse rating in Table 7.20 to Table 7.23.
Drive
modules in
system
FC 302
modules
[kW]
FC 102 and FC
202 modules
[kW]
Recommended
fuse (maximum)
2 N250 N315 aR-630
2 N315 N355 aR-630
2 N355 N400 aR-630
2 N400 N450 aR-800
2 N450 N500 aR-800
4 N500 N560 aR-900
4 N560 N630 aR-900
4 N630 N710 aR-1600
4 N710 N800 aR-1600
4 N800 N1M0 aR-1600
Table 7.20 12-Pulse Drive Systems (380–500 V AC)
Any minimum 500 V UL-listed fuse can be used for the 380–500 V AC
drive systems.
Drive
modules in
system
FC 302
modules
[kW]
FC 102 and FC
202 modules
[kW]
Recommended
fuse (maximum)
2 N450 N500 aR-1600
4 N500 N560 aR-2500
4 N560 N630 aR-2500
4 N630 N710 aR-2500
4 N710 N800 aR-2500
4 N800 N1M0 aR-2500
Table 7.21 6-Pulse Drive Systems (380–500 V AC)
Any minimum 500 V UL-listed fuse can be used for the 380–500 V AC
drive systems.
Drive
modules in
system
FC 302
modules
[kW]
FC 102 and
FC 202
modules [kW]
Recommended
fuse (maximum)
2 N250 N315 aR-550
2 N315 N355 aR-630
2 N355 N400 aR-630
2 N400 N500 aR-630
2 N500 N560 aR-630
2 N560 N630 aR-900
4 N630 N710 aR-900
4 N710 N800 aR-900
4 N800 N900 aR-900
4 N900 N1M0 aR-1600
4 N1M0 N1M2 aR-1600
Table 7.22 12-Pulse Drive Systems (525–690 V AC)
Any minimum 700 V UL-listed fuse can be used for the 525–690 V AC
drive systems.
Drive
modules in
system
FC 302
modules
[kW]
FC 102 and FC
202 modules
[kW]
Recommended
fuse (maximum)
4 N630 N710 aR-1600
4 N710 N800 aR-2000
4 N800 N900 aR-2500
4 N900 N1M0 aR-2500
4 N1M0 N1M2 aR-2500
Table 7.23 6-Pulse Drive Systems (525–690 V AC)
Any minimum 700 V UL-listed fuse can be used for the 525–690 V AC
drive systems.
7.3.3 Fuse Replacement
If it becomes necessary to replace an AC or DC fuse, refer to the VLT
®
FC Series, D-frame Service Manual and the VLT
®
Parallel
Drive Modules DC Fuses Installation Instructions.
7.3.4 Short Circuit Current Rating (SCCR)
The drive modules are supplied with built-in AC fuses. The modules have been qualied for 100 kA short circuit current
rating (SCCR) for the standard busbar congurations at all voltages (380–690 V AC). For more information on short-circuit
protection of the drive modules, see chapter 7.3.1 Protection. For more information on the recommended fuses for CE or UL
compliance, see chapter 7.3.2.1 Recommended Fuses for CE Compliance or chapter 7.3.2.2 Recommended Fuses for UL
Compliance, respectively.
Specications