7.3.2.1 Recommended Fuses for CE Compliance
Drive
modules
in
system
FC 302
modules
[kW]
FC 102
and FC
202
modules
[kW]
Recommended
fuse
Recommended
fuse
(maximum)
2 N250 N315 aR-630 aR-630
2 N315 N355 aR-630 aR-630
2 N355 N400 aR-630 aR-630
2 N400 N450 aR-800 aR-800
2 N450 N500 aR-800 aR-800
4 N500 N560 aR-900 aR-900
4 N560 N630 aR-900 aR-900
4 N630 N710 aR-1600 aR-1600
4 N710 N800 aR-1600 aR-1600
4 N800 N1M0 aR-1600 aR-1600
Table 7.16 12-Pulse Drive Systems (380–500 V AC)
Drive
modules
in
system
FC 302
modules
[kW]
FC 102
and FC
202
modules
[kW]
Recommended
fuse
Recommended
fuse
(maximum)
2 N450 N500 aR-1600 aR-1600
4 N500 N560 aR-2500 aR-2500
4 N560 N630 aR-2500 aR-2500
4 N630 N710 aR-2500 aR-2500
4 N710 N800 aR-2500 aR-2500
4 N800 N1M0 aR-2500 aR-2500
Table 7.17 6-Pulse Drive Systems (380–500 V AC)
Drive
modules
in
system
FC 302
modules
[kW]
FC 102
and FC
202
modules
[kW]
Recommended
fuse
Recommended
fuse
(maximum)
2 N250 N315 aR-550 aR-550
2 N315 N355 aR-630 aR-630
2 N355 N400 aR-630 aR-630
2 N400 N500 aR-630 aR-630
2 N500 N560 aR-630 aR-630
2 N560 N630 aR-900 aR-900
4 N630 N710 aR-900 aR-900
4 N710 N800 aR-900 aR-900
4 N800 N900 aR-900 aR-900
4 N900 N1M0 aR-1600 aR-1600
4 N1M0 N1M2 aR-1600 aR-1600
Table 7.18 12-Pulse Drive Systems (525–690 V AC)
Drive
modules
in
system
FC 302
modules
[kW]
FC 102
and FC
202
modules
[kW]
Recommended
fuse
Recommended
fuse
(maximum)
4 N630 N710 aR-1600 aR-1600
4 N710 N800 aR-2000 aR-2000
4 N800 N900 aR-2500 aR-2500
4 N900 N1M0 aR-2500 aR-2500
4 N1M0 N1M2 aR-2500 aR-2500
Table 7.19 6-Pulse Drive Systems (525–690 V AC)
Specications User Guide
MG37L202 Danfoss A/S © 08/2017 All rights reserved. 69