Conventions
Numbered lists show procedures.
Bullet lists show additional information.
Italicized text shows cross-references, links, and parameters.
All measurements are presented as metric units (imperial units).
8.2 International/North American Default Parameter Settings
Setting parameter 0-03 Regional Settings to [0] International or [1] North America changes the default settings for some
parameters. Table 8.2 lists those parameters that are
aected. Changes made to the default settings are stored. They are
available for viewing in the quick menu, along with any programming entered into the parameters.
Parameter International Default Parameter Value North American Default Parameter Value
Parameter 0-03 Regional Settings International North America
Parameter 0-71 Date Format DD-MM-YYYY MM/DD/YYYY
Parameter 0-72 Time Format 24 h 12 h
Parameter 1-20 Motor Power [kW]
See Note
1)
See Note
1)
Parameter 1-21 Motor Power [HP]
See Note
2)
See Note
2)
Parameter 1-22 Motor Voltage 230 V/400 V/575 V 208 V/460 V/575 V
Parameter 1-23 Motor Frequency 50 Hz 60 Hz
Parameter 3-03 Maximum Reference 50 Hz 60 Hz
Parameter 3-04 Reference Function Sum External/Preset
Parameter 4-13 Motor Speed High Limit [RPM]
3)
1500 RPM 1800 RPM
Parameter 4-14 Motor Speed High Limit [Hz]
4)
50 Hz 60 Hz
Parameter 4-19 Max Output Frequency 100 Hz 120 Hz
Parameter 4-53 Warning Speed High 1500 RPM 1800 RPM
Parameter 5-12 Terminal 27 Digital Input Coast inverse External interlock
Parameter 5-40 Function Relay Alarm No alarm
Parameter 6-15 Terminal 53 High Ref./Feedb.
Value
50 60
Parameter 6-50 Terminal 42 Output Speed 0–HighLim Speed 4–20 mA
Parameter 14-20 Reset Mode Manual reset Innite auto reset
Parameter 22-85 Speed at Design Point [RPM]
3)
1500 RPM 1800 RPM
Parameter 22-86 Speed at Design Point [Hz] 50 Hz 60 Hz
Parameter 24-04 Fire Mode Max Reference 50 Hz 60 Hz
Table 8.2 International/North American Default Parameter Settings
1) Parameter 1-20 Motor Power [kW] is visible only when parameter 0-03 Regional Settings is set to [0] International.
2) Parameter 1-21 Motor Power [HP]is visible only when parameter 0-03 Regional Settings is set to [1] North America.
3) This parameter is visible only when parameter 0-02 Motor Speed Unit is set to [0] RPM.
4) This parameter is visible only when parameter 0-02 Motor Speed Unit is set to [1] Hz.
8.3
Parameter Menu Structure
Certain parameters are specic to the drive system. For a list of these parameters and all other system parameters, including
descriptions, refer to the programming guide applicable to the series of drive modules used in creating the drive system.
Appendix
VLT
®
Parallel Drive Modules
72 Danfoss A/S © 08/2017 All rights reserved. MG37L202
88

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals