15-06 Reset kWh Counter
Default value: [0] Do not reset
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: True
Table 271: Option:
[0]
Do not reset
Do not reset.
[1]
Reset counter
Select this option and press [OK] to reset the kWh counter to 0 (see parameter 15-02 kWh Counter).
15-07 Reset Running Hours Counter
Default value: [0] Do not reset
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: True
Table 272: Option:
[0]
Do not reset
Do not reset.
[1]
Reset counter
Select this option and press [OK] to reset the running hours counter to 0 (see parameter 15-01 Running
Hours).
4.12.2 15-3* Alarm Log
Parameters in this group are array parameters, where up to 10 fault logs can be viewed. [0] is the most recent logged data, and [9]
the oldest. Fault codes, values, and time stamp can be viewed for all logged data.
15-30 Alarm Log: Error Code
Default value: 0
Parameter type: Range
2-setup: 1 setup
Conversion index: 0
Data type: u_int16
Change during operation: True
View the fault code and lookup its meaning in chapter Troubleshooting.
Table 273: Range:
Min: 0
Max: 255
Default value: 0
15-31 InternalFaultReason
Default value: 0
Parameter type: Range
2-setup: 1 setup
Conversion index: 0
Data type: int16
Change during operation: True
View a description of the error. This parameter is used with alarm 38, Internal Fault.
Table 274: Range:
Min: -32767
Max: 32767
Default value: 0
15-32 Alarm Log: Time
Default value: 0 s
Parameter type: Range
2-setup: All setups
Conversion index: 0
Data type: u_int32
Change during operation: False
View the time when the logged event occurred. Time is measured in seconds from the drive start-up.
Table 275: Range:
Min: 0 s
Max: 2147483647
Default value: 0 s
AU363928304090en-000101 / 130R0982140 | Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide

Table of Contents

Other manuals for Danfoss VLT Flow Drive FC 111

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Flow Drive FC 111 and is the answer not in the manual?

Danfoss VLT Flow Drive FC 111 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Flow Drive FC 111
CategoryDC Drives
LanguageEnglish

Related product manuals