16 | Danfoss Drives · DKDD.PB.551.A1.02
Soft starters are much more exible than auto-transformer starters
and provide a much smoother start, generally at a lower cost.
Auto-transformer starters cannot accommodate varying load
conditions (e.g. loaded or unloaded starts) and the start torque
cannot be freely adjusted to match motor and load characteristics.
Damaging torque and current transients still occur at the steps
between voltages, and auto-transformer starters are not capable
of providing soft stop. Auto-transformer starters are large and
expensive, especially if high start frequency is required.
Auto-Transformer Starters: How does soft start
compare to auto-transformer starting?
To assist your service engineer, they require the following
information:
Model and serial number of the soft starter
Motor kW and FLC
Main supply voltage and frequency
Control voltage
Application (e.g. pump, compressor)
Time installed before failure
Details of other soft starters on the supply bus. Are these failing?
If the soft starter trips, details of the code and mode of operation
The installation’s power and control schematic diagram
Fault nding: What are the key questions?

Other manuals for Danfoss VLT MCD 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT MCD 202 and is the answer not in the manual?

Danfoss VLT MCD 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT MCD 202
CategoryController
LanguageEnglish

Related product manuals