Danfoss Drives · DKDD.PB.551.A1.02 | 49
This requires an MCD DeviceNet Module which clips onto the side
of the MCD 500 (Cat. No: 175G9002).
Notes
• A single DeviceNet Module is required for each MCD 500.
• DeviceNet node address (MAC ID) and data rate are selected
using three rotary switches on the DeviceNet Module.
• Up to 63 DeviceNet Modules can be used as DeviceNet slaves on
a single DeviceNet network.
• The DeviceNet Module is powered via the network cable.
• The MCD DeviceNet Module is ODVA tested and certified.
• For more information on the MCD DeviceNet Module, refer to the
Installation Instructions (MG.17.Hx.02), located at
www.danfoss.com/drives.
MCD500
MCD
DeviceNet
Module
RD
(V+)
WH
(CAN-H)
BK
(V-)
BU
(CAN-L)
(SHIELD)
Standard 5-wire
connection onto a
DeviceNet network.
120 termination
resistors are required
at end of each end
of the network cable.
Cat. No: 175G9002
(Auto On mode)
MCD 500 DeviceNet Option