Danfoss Drives · DKDD.PB.551.A1.02 | 49
This requires an MCD DeviceNet Module which clips onto the side
of the MCD 500 (Cat. No: 175G9002).
Notes
A single DeviceNet Module is required for each MCD 500.
DeviceNet node address (MAC ID) and data rate are selected
using three rotary switches on the DeviceNet Module.
Up to 63 DeviceNet Modules can be used as DeviceNet slaves on
a single DeviceNet network.
The DeviceNet Module is powered via the network cable.
The MCD DeviceNet Module is ODVA tested and certified.
For more information on the MCD DeviceNet Module, refer to the
Installation Instructions (MG.17.Hx.02), located at
www.danfoss.com/drives.
MCD500
MCD
DeviceNet
Module
RD
(V+)
WH
(CAN-H)
BK
(V-)
BU
(CAN-L)
(SHIELD)
Standard 5-wire
connection onto a
DeviceNet network.
120 termination
resistors are required
at end of each end
of the network cable.
Cat. No: 175G9002
(Auto On mode)
MCD 500 DeviceNet Option